background image

Subject to modifications.

© Vestamatic GmbH

Art.-Nr.: 

3060 001 GB 4518 A06  •  Vestamatic GmbH  •  Dohrweg 27  •  D-41066 Mönchengladbach 

 •  www.vestamatic.com

5/10

G

IF SMI RS-485 DIN

6.3.8  MSG_SET_POS_STEP_UP

This message is used to move all, or a set of venetian blinds, to an absolute 

position combined with an relative 

up

 command.

Message:

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [POS0] / [POS1] / 

[NSTEP] /  [CRC16]

[MSK0]:  

LSB of 16-bit mask to select motor address 0..7.

[MSK1]:  

MSB of 16-bit mask to select motor address 8..16.

[POS0]:  

LSB of 16-bit absolute position.

[POS1]: 

MSB of 16-bit absolute position.

[NSTEP]:  Number of steps (1..255) in 

UP

 direction. 1 step is defined as 

2º rotation of the output shaft of the SMI motor.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT. The position of each sun blind can be 

obtained by the detailed response message MSG_GETDETSTAT.

6.3.9  MSG_SET_POS_STEP_DOWN

This message is used to move all, or a set of venetian blinds, to an absolute 

position combined with an relative 

down

 command.

Message:

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [POS0] / [POS1] / 

[NSTEP] /  [CRC16]

[MSK0]:  

LSB of 16-bit mask to select motor address 0..7.

[MSK1]:  

MSB of 16-bit mask to select motor address 8..16.

[POS0]:  

LSB of 16-bit absolute position.

[POS1]: 

MSB of 16-bit absolute position.

[NSTEP]:  Number of steps (1..255) in 

DOWN

 direction. 1 step is defined 

as 2º rotation of the output shaft of the SMI motor.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT. The position of each sun blind can be 

obtained by the detailed response message MSG_GETDETSTAT.

6.3.10  MSG_GOTO_POS 

1

This message is used to move all, or a set of venetian blinds, to inter-

mediate position 1.

Message:

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [CRC16]

[MSK0]:  

LSB of 16-bit mask to select motor address 0..7.

[MSK1]:  

MSB of 16-bit mask to select motor address 8..16.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT. The position of each sun blind can be 

obtained by the detailed response message MSG_GETDETSTAT.

6.3.11  MSG_GOTO_POS 

2

This message is used to move all, or a set of venetian blinds, to inter-

mediate position 2.

Message:

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [CRC16]

[MSK0]:  

LSB of 16-bit mask to select motor address 0..7.

[MSK1]:  

MSB of 16-bit mask to select motor address 8..16.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT. The position of each sun blind can be 

obtained by the detailed response message MSG_GETDETSTAT.

6.3.12 MSG_GETMANID

This message is used to request the manufacturer ID of a specific motor.

Message:

  [SID] / [LEN] / [CMND] / [SMIID] / [CRC16] 

[SMIID]: 

SMI address of motor (0..15).

Response: 

[SID] / [LEN] / [CMND] / [SMIID] / [MID] / [CRC16]

[MID]: 

bit3-0:  Manufacturer ID. (See SMI-Group website for actual 

list)

   

Bit7-4:  Motor type. An indication from 0 to 15 which each 

SMI motor manufacturer can freely use to identify 

their SMI motor type.

REMARK:

  An Manufacturer ID of 0 indicates that an invalid SMI-ID is 

used.

6.3.4  MSG_STEP_UP

This message is used to relatively move all, or a set of sun blind, in 

UP 

direction.

Message: 

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [NSTEP] / [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

[NSTEP]: 

Number of steps (1..255) in 

UP

 direction. 1 step is defined as 

 

2° rotation of the output shaft of the SMI motor.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

6.3.5  MSG_STEP_DOWN

This message is used to relatively move all, or a set of sun blind, in 

DOWN 

direction.

Message: 

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [NSTEP] / [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

[NSTEP]: 

Number of steps (1..255) in 

DOWN

 direction. 1 step is defined 

 as 

2° rotation of the output shaft of the SMI motor.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

6.3.6  MSG_SET_POS

This message is used to move all, or a set of sun blind, to an absolute 

position.

Message: 

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [POS0] / [POS1] / 

 [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

[POS0]: 

LSB of 16-bit absolute position.

[POS1]: 

MSB of 16-bit absolute position.

The absolute position value is defined as below:
 

0x0000 is the top position (0%).

 

0x8000 is the middle position (50%).

 

0xFFFF is the bottom position (100%).

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

6.3.7  MSG_SET_TILT

This message is used to move all, or a set of venetian blinds, in a absolute 

tilt orientation.

Message:

   [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [TILT] / [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

[TILT]: 

Absolute tilt orientation (0..255).

Absolute tilt orientation is defined as follow:
 

127 

(0x7F) slats completely closed in down direction

 

0      

(0x00) slats completely open (horizontal)

 

-128 

(0x80) slats completely closed in up direction

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

REMARK:

  The MSG_SET_TILT message uses a manufacturer specific 

SMI command, which is currently only supported by Vesta-

matic SMI motors.

Содержание IF SMI RS-485 230 VAC-DIN

Страница 1: ...hould spread high value solutions and promote drives and controls on the market The applications in roller shutters and sun protection systems require extreme robustness and economic efficiency SMI ha...

Страница 2: ...Long press Modify current base address Double press Show error log UP DOWN button In main menu Steer all attached SMI motors UP DOWN In address menu Increase Decrease base address Error log menu Show...

Страница 3: ...n twice within 1 second The text Er is briefly visible to indicate that the error log is shown Next the last occurred error is shown blinking By pressing the UP button the previous occurred error will...

Страница 4: ...3 1 MSG_UP This message is used to move all or a set of sun blind to the top position Message SID LEN CMND MSK0 MSK1 CRC16 MSK0 LSB of 16 bit mask to select motor address 0 7 MSK1 MSB of 16 bit mask t...

Страница 5: ...0 Manufacturer ID See SMI Group website for actual list Bit7 4 Motor type An indication from 0 to 15 which each SMI motor manufacturer can freely use to identify their SMI motor type REMARK An Manufac...

Страница 6: ...G_ERROR Request gateway options Message SID LEN CMND CRC16 Response SID LEN CMND OPTIONS CRC16 OPTIONS Stored gateway options See gateway options layout as described above Default gateway options 0x00...

Страница 7: ...of 16 bit intermediate position 2 POS1 MSB of 16 bit intermediate position 2 6 4 1 MSG_VERSION This message is used to check to version number of the application Message SID LEN CMND CRC16 Response SI...

Страница 8: ...lt information uses a manufacturer specific SMI command which is currently only supported by Vestamatic SMI motors For non Vestamatic SMI motors TILT value 0x00 is returned CYCLE0 3 32 bits cycle coun...

Страница 9: ...n be set from 0 to 15 Next press a command button like GET_SERIAL GET_PARAM SET_SMI_ID GET_POS1 SET_POS1 GET_POS2 SET_POS2 or GETDETSTAT REMARK Some commands need additional parameters See section 6 P...

Страница 10: ...GmbH Art Nr 3060 001 GB 4518 A06 Vestamatic GmbH Dohrweg 27 D 41066 M nchengladbach www vestamatic com 10 10 G IF SMI RS 485 DIN 8 1 Wiring diagram IF SMI RS 485 24VDC DIN 8 2 Wiring diagram IF SMI R...