IF SMI RS-485 DIN

6.2  CRC16 Calculation

Example code CRC16 calculation in C-language:

#define CRC_CONSTANT 

0xA001

word Crc16 (byte* pb, byte len)
{
 

byte i;

 

word crc;

 

for (crc=0xffff; len--; pb++)

 {
 

 

crc ^= (byte)*pb;

 

 

for (i=8; i--; )

 

 

 

if (crc & 0x01)

   {
    crc 

>>= 

1;

    crc 

^= 

CRC_CONSTANT;

   }
   else
    crc 

>>= 

1;

 }
 

// return crc result

 

return crc;

}

6.  Protocol

This chapter describes the communication protocol between the IF SMI RS-485 module 

and Host controller.

6.3  Steer commands

#define MSG_UP 

0x10

#define MSG_DOWN 

0x11

#define MSG_STOP 

0x12

#define MSG_STEP_UP 

0x13

#define MSG_STEP_DOWN 

0x14

#define MSG_SET_POS 

0x15

#define MSG_SET_TILT 

0x16

#define MSG_SET_POS_STEP_UP  0x17
#define MSG_SET_POS_STEP_DOWN 0x18
#define MSG_GOTO_POS1 

0x19

#define MSG_GOTO_POS2 

0x1A

#define MSG_GETMANID 

0x2C

#define MSG_SMI_TUNNEL

 0x2D

#define MSG_GW_OPTIONS

 0x50

#define MSG_ERROR

 0xE0

6.1  Message structure

[SID] [LEN] [CMD] [DATA] [CRC16]
SID 

Slave ID

LEN 

Message length (without CRC)

CMD 

Command byte

DATA 

Optional data bytes

CRC16 

16 bits checksum (LSB first)

The IF SMI RS-485 module has 4 

DIP  switches, which represents the base 

address of the module from 0 to 15 (decimal) 

or 0 to F (hexadecimal). The base address 

is part of the Slave ID:

Base address

Slave ID

0

0xC0

1

0xC1

2

0xC2

3

0xC3

4

0xC4

5

0xC5

6

0xC6

7

0xC7

8

0xC8

9

0xC9

10

0xCA

11

0xCB

12

0xCC

13

0xCD

14

0xCE

15

0xCF

6.3.1  MSG_UP

This message is used to move all, or a set of sun blind, to the 

top

 position.

Message: 

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

When bit 

n

  in mask is set, SMI motor with address 

n

 is addressed and 

executes a 

UP

 command.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

6.3.2  MSG_DOWN

This message is used to move all, or a set of sun blind, to the 

lower

 position.

Message: 

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

When bit 

n

  in mask is set, SMI motor with address 

n

 is addressed and 

executes a 

DOWN

 command.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

6.3.3  MSG_STOP

This message is used to stop all, or a set of sun blind.

Message: 

  [SID] / [LEN] / [CMND] / [MSK0] / [MSK1] / [CRC16]

[MSK0]: 

LSB of 16-bit mask to select motor address 0..7.

[MSK1]: 

MSB of 16-bit mask to select motor address 8..16.

The IF SMI RS-485 module responds to this request with a general status 

message MSG_GETGENSTAT.

The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT. The IF SMI RS-485 module responds to 

this request with a general status message MSG_GETGENSTAT.
The position of each sun blind can be obtained by the detailed response 

message MSG_GETDETSTAT.

Содержание IF SMI RS-485 230 VAC-DIN

Страница 1: ...hould spread high value solutions and promote drives and controls on the market The applications in roller shutters and sun protection systems require extreme robustness and economic efficiency SMI ha...

Страница 2: ...Long press Modify current base address Double press Show error log UP DOWN button In main menu Steer all attached SMI motors UP DOWN In address menu Increase Decrease base address Error log menu Show...

Страница 3: ...n twice within 1 second The text Er is briefly visible to indicate that the error log is shown Next the last occurred error is shown blinking By pressing the UP button the previous occurred error will...

Страница 4: ...3 1 MSG_UP This message is used to move all or a set of sun blind to the top position Message SID LEN CMND MSK0 MSK1 CRC16 MSK0 LSB of 16 bit mask to select motor address 0 7 MSK1 MSB of 16 bit mask t...

Страница 5: ...0 Manufacturer ID See SMI Group website for actual list Bit7 4 Motor type An indication from 0 to 15 which each SMI motor manufacturer can freely use to identify their SMI motor type REMARK An Manufac...

Страница 6: ...G_ERROR Request gateway options Message SID LEN CMND CRC16 Response SID LEN CMND OPTIONS CRC16 OPTIONS Stored gateway options See gateway options layout as described above Default gateway options 0x00...

Страница 7: ...of 16 bit intermediate position 2 POS1 MSB of 16 bit intermediate position 2 6 4 1 MSG_VERSION This message is used to check to version number of the application Message SID LEN CMND CRC16 Response SI...

Страница 8: ...lt information uses a manufacturer specific SMI command which is currently only supported by Vestamatic SMI motors For non Vestamatic SMI motors TILT value 0x00 is returned CYCLE0 3 32 bits cycle coun...

Страница 9: ...n be set from 0 to 15 Next press a command button like GET_SERIAL GET_PARAM SET_SMI_ID GET_POS1 SET_POS1 GET_POS2 SET_POS2 or GETDETSTAT REMARK Some commands need additional parameters See section 6 P...

Страница 10: ...GmbH Art Nr 3060 001 GB 4518 A06 Vestamatic GmbH Dohrweg 27 D 41066 M nchengladbach www vestamatic com 10 10 G IF SMI RS 485 DIN 8 1 Wiring diagram IF SMI RS 485 24VDC DIN 8 2 Wiring diagram IF SMI R...

Отзывы: