G
IF SMI RS-485 DIN
5.4 Address menu
The current RS-485 base address is shown when the MODE button is
pressed shortly (< 5 sec).
As long as the MODE button is pressed shortly,
“Ad” is shown on the display.
When the MODE button is released, the current
RS-485 base address is shown for 5 sec.
To directly return to the main menu, the MODE button must be pressed
again.
5.5 Modify base address
The current RS-485 base address can be modified be pressing the
MODE button for more than 5 seconds (after 5 seconds the text “Ad” starts
blinking).
After the MODE button is released, the current RS-485 base address is
shown blinking.
– Pressing UP will increase the RS-485 base address.
– Pressing DOWN will decrease the RS-485 base address.
– Pressing MODE button – or wait for 5 seconds – will store the RS-485
base address and return to main menu.
The RS-485 base address can be modified from 0 to 15.
When pressing the DOWN button while base ad-
dress is already 0, the following is shown to indicate
that the base address cannot be further decreased.
When pressing the UP button while the base address
is already 15, the following is shown to indicate that
the base address cannot be further increased.
5.6 Show error
When an error occurs,
this will be shown directly.
5.7 Error log menu
The error log keeps track of the 5 last occurred errors, and can be shown
be pressing the MODE button twice within 1 second.
The text “Er” is briefly visible to indicate that the error
log is shown.
Next, the last occurred error is shown blinking.
– By pressing the UP button, the previous occurred error will be shown.
– By pressing the DOWN button, the next occurred error will be shown.
When pressing DOWN button while first error in log
is currently being shown..
When pressing UP button while last error in log is
currently shown.
By briefly pressing MODE button – or waiting for a few seconds – you will
return back to main menu.
5.8 Soft RESET
The IF SMI RS-485 can be restarted (soft-reset) without interruption of the
power supply by pressing the MODE button for 10 seconds.
After 10 seconds pressing the MODE button, the soft-reset will be entered,
and display will briefly show the following:
5.3 Menu navigation
When the UP or DOWN buttons in the main menu are pressed, all attached
SMI motors will move UP or DOWN (depends on the pressed button) as
long as the button is pressed. This feature is useful during commissioning
to check:
– if the SMI communication is working
– if all attached motors are running in the correct direction
– if the limit positions are set correctly
Display shows the following as a visual feedback:
UP button
pressed
DOWN button
pressed
Error code description:
E0
= no error
E1
= RS-485 framing error
E2
= RS-485 timing error
E3
= RS-485 data overflow error
E4
= RS-485 CRC error
E5
= RS-485 command error (not supported or invalid length)
E6
= RS-485 busy (not able to process new command)
E7
= SMI format error
E8
= SMI checksum error
E9
= SMI timing error
EA
= SMI data overflow
EB
= SMI echo error
EC
= SMI queue full error
The error message is shown for 5 seconds. Pressing any buton returns to
main menu directly.