IF SMI KNX 24VDC
Subject to modifications.
11/15
G
ETS parameters
(Parameter presets are in bold)
Parameter
Setting
Description
Dependent on
Factor for the number
of degrees of angle for
maximum opened slat
position (Basis: 2°)
0–255
45
This parameter is used to determine the angle of the slat
position from fully closed to fully opened for all channels.
and shade type
= “blind”
Safety
(e.g. wind alarm)
released
locked
This parameter can be used to set whether the safety object
and the safety function are active for the particular channel.
Travel command
for safety
no action
travel upwards
travel downwards
This parameter can be used to determine whether the particular
drive needs to travel upwards, travel downwards or keep its
position in the event of a safety alarm. Independent of this
parametrisation, all incoming travel commands via the EIB
are locked if the safety function is released and switched on.
and safety
= “released”
Restore positions
after all-clear
locked
released
If automatic mode is deactivated, this parameter can be used to
indicate for the particular channel that %-positions, which were
received as manual mode objects, should be moved to again or
moved to subsequently following the safety alarm all-clear.
and automatic mode
= “locked”
Travel command lock
released
locked
This parameter can be used to set whether the travel command
lock is active for the particular channel. If the lock is released
and switched on, all incoming travel commands via the EIB
will be blocked.
Behaviour during bus
voltage failure
no action
travel upwards
travel downwards
This parameter can be used to determine whether the particular
drive needs to travel upwards, travel downwards or keep its
position during bus voltage failure.
Behaviour during bus
voltage recovery
no action
travel upwards
travel downwards
This parameter can be used to determine whether the particular
drive needs to travel upwards, travel downwards or keep its
position during bus voltage recovery.
Automatic mode
locked
released
This parameter can be used to determine whether the particular
channel supports automatic mode. If the “Released” setting is
selected, the objects “Sunshade”, “Position of sunshade” and
“Position of slat angle” will only be effective if automatic mode is
active. Otherwise they will just be stored and only implemented
at a later stage when automatic mode is activated. If the
“Locked” setting is selected, the objects “Position of sunshade”
and “Position of slat angle” will be interpreted as manual mode
objects.
Factor for the number
of degrees of angle for
slat position from open
to shade height change
(Basis: 2°)
0–255
30
This parameter can be used for all channels to set the angle
by which the slats will turn when moving up or when adjusting
upwards beyond the fully opened position, before the shade
height changes.
and shade type
= “roller shutter”
“Mechanics” tab
Parametrisation
of drives = “all equal”
“Admin #” tab (# is channel number 1 … 8)
Parametrisation of
drives = “individual” and
use of drive # = “used”