31
Connections to List 21, 31 Module Mounting Assembly
Spec. No. 588706000 List 21, 31 Module Mounting Assembly provides an AC input line cord and plug. Refer to
CAUTION!
AC input sized for module mounting assembly population of rectifier and BBU modules as shown
in Figure 18. DO NOT populate slots in any other arrangement than what is shown in Figure 18. Failure to
follow this requirement could result in tripping of AC input protection devices.
Figure 18
:
AC Input Connections to a 588706000 List 21, 31 Module Mounting Assembly
AC Input Connections, 588706000 List 21, 31
Nominal 200 VAC / 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-Phase, 1 Feed per Module Mounting Assembly
(1 Feed per 9 Module Positions)
Rear (Main Module Mounting Assembly Shown, Expansion Module Mounting Assembly Similar)
AC Feed #1
(Positions #1 - #9)
200 VAC / 208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #1 - #3
L2 - L3: Position #4 - #6
L1 - L3 : Position #7 - #9
60 AMP
Hubbell
P/N HBL460P9W
or equivalent
4 AWG
L2
GND
L1
L3
Front (Main Module Mounting Assembly Shown, Expansion Module Mounting Assembly Similar)
Rectifier Module / BBU Module Mounting Positions
Rect.
Rect.
Rect.
Rect.
or
BBU*
Rect.
or
BBU*
Rect.
or
BBU*
BBU
BBU
BBU
#1 #2 #3 #4 #5 #6 #7 #8 #9
* Maximum of four (4) rectifiers
allowed in the system.
If multiple List 21 / 31 shelves are
connected to the same AC mains,
the fourth rectifier module should
be placed in different positions in
the subsequent shelves to balance
the AC line currents.