Vertiv
|
NetXtend +12 VDC Bulk Output Power System Installation and User Manual (UM588706000)
|
Rev. H
8
Main Module Mounting Assembly (N+1 Redundant)
The main module mounting assembly houses up to nine (9) modules, plus the SCC controller. Modules can be a
combination of rectifier modules and BBU (Battery Backup Unit) modules, depending on the AC input configuration.
See SAG588706000 for restrictions.
SCC (System Control Card) Controller: The controller provides power system control, monitoring functions, and
local/remote alarm functions. The controller also provides data acquisition, system alarm management, and
advanced battery management. The controller provides an Ethernet port for remote access. It also comes with
SNMP capability for remote system management. Operation of the SCC controller requires a master upstream
supervisory and control unit, such as the Avocent UMG, connected to the system’s Ethernet port and utilizing an
SNMP interface. Refer to the SCC Controller Instructions (UM1M520HNA) for more information.
NOTE!
The rectifier and BBU modules will continue to operate if the SCC controller fails. The rectifier and
BBU modules will work if the system is powered up without an SCC controller; however, an SCC controller is
required to get any monitoring/status information from the system. The application should be designed with
an SCC controller.
Expansion Module Mounting Assembly (N+1 Redundant)
Each expansion module mounting assembly houses up to nine (9) modules. Modules can be a combination of
rectifier modules and BBU (Battery Backup Unit) modules, depending on the AC input configuration. See
SAG588706000 for restrictions.
Rectifier Modules
The system may contain rectifier modules, which provide load power. Refer to the Rectifier Instructions
(UM1R123000) for more information.
BBU (Battery Backup Unit) Modules
The system may contain BBU modules, which provide power during AC utility failures, and can provide additional
power on demand. Each BBU module is equipped with a rectifier / charger, a lithium-ion battery pack, and a 12 VDC
converter. The BBU module is designed to provide 3 kW of 12 VDC power for a minimum of 90 seconds, per module.
Refer to the BBU Instructions (UM1B123000) for more information.
Содержание NetSure PSS12/2000-19B
Страница 44: ...UM582127000100 11AD1209MU RH 06 17...