Vertiv
|
NetXtend +12 VDC Bulk Output Power System Installation and User Manual (UM588706000)
|
Rev. H
23
Connections to List 2, 12 Module Mounting Assembly
Spec. No. 588706000 List 2, 12 Module Mounting Assembly provides AC input terminal blocks behind a rear access
panel. The rear access panel contains three cord grips. Refer to
Figure 10:
AC Input Connections to a 588706000 List 2, 12 Module Mounting Assembly
AC Input Connections, 588706000 List 2, 12
Nominal 200 VAC / 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-Phase, 3 Feeds per Module Mounting Assembly
(1 Feed per 3 Module Positions)
AC Feed #3
(Positions #7 - #9)
200 VAC / 208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #7
L2 - L3: Position #8
L1 - L3: Position #9
AC Feed #2
(Positions #4 - #6)
200 VAC / 208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #4
L2 - L3: Position #5
L1 - L3: Position #6
AC Feed #1
(Positions #1 - #3)
200 VAC / 208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #1
L2 - L3: Position #2
L1 - L3: Position #3
GND
L1
L2
L2
L2
L3
GND
L1
L3
GND
L1
L3
Front (Main Module Mounting Assembly Shown, Expansion Module Mounting Assembly Similar)
Rectifier Module / BBU Module
Mounting Positions
#1 #2 #3 #4 #5 #6 #7 #8 #9
FRAME GROUND CONNECTION
One M4 stud and hardware.
Torque: 1.7 Nm (15 in-lbs.)
AC INPUT
Wire Size Capacity:
16 to 4 AWG.
Torque:
2.5 to 3.0 Nm (22.1 to 26.5 in-lbs.)
Rear (Main Module Mounting Assembly Shown, Expansion Module Mounting Assembly Similar)
(back panel removed for clarity only)
Содержание NetSure PSS12/2000-19B
Страница 44: ...UM582127000100 11AD1209MU RH 06 17...