NetSure™
+12 VDC Bulk Output Power System
Installation and User Manual (UM588706000), Revision H
Specification Number: 588706000 Model Number: PSS12/2000-19BC, PSS12/2200-19BC, PSS12/2000-19B, PSS12/2200-19B
Страница 1: ...NetSure 12 VDC Bulk Output Power System Installation and User Manual UM588706000 Revision H Specification Number 588706000 Model Number PSS12 2000 19BC PSS12 2200 19BC PSS12 2000 19B PSS12 2200 19B...
Страница 2: ...amages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be used in pe...
Страница 3: ...10 General Requirements 10 Inspecting the Equipment and Storing for Delayed Installations 10 General 10 Securing the Module Mounting Assembly s to the Mounting Rails of an IT Rack 11 Installing Shippi...
Страница 4: ...ructions 37 Initial Startup Preparation 37 Initially Starting the System 37 Operating Procedures 39 SCC Controller Rectifier Module and BBU Module 39 Local Indicators 39 Maintenance 40 System Maintena...
Страница 5: ...njury if not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standard...
Страница 6: ...be completely disconnected from the branch circuits wiring used to provide power to the system before any AC electrical connections are made Follow local lockout tagout procedures to ensure upstream b...
Страница 7: ...mer waste recycling plans for electronics and battery disposal The BBU module must be handled carefully The BBU module is FRAGILE and contains lithium ion battery cells If the BBU module shows ANY sig...
Страница 8: ...resistor no external resistor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing...
Страница 9: ...C Bulk Output Module Mounting Assembly is a complete integrated power system containing rectifiers BBU s Battery Backup Units intelligent control and monitoring The NetSure PSS12 2000 19B and PSS12 22...
Страница 10: ...formation NOTE The rectifier and BBU modules will continue to operate if the SCC controller fails The rectifier and BBU modules will work if the system is powered up without an SCC controller however...
Страница 11: ...list has been checked NOTE The system is not powered up until the end of this checklist NOTE Some of these procedures may have been performed at the factory for you Installing the System Equipment Ins...
Страница 12: ...g rails of an IT rack Rectifier module BBU module and module mounting assembly ventilating openings must not be blocked and temperature of air entering these must not exceed rated operating ambient te...
Страница 13: ...Refer to the BBU Instructions UM1B123000 for more information Securing the Module Mounting Assembly s to the Mounting Rails of an IT Rack Install the module mounting assembly s into a 19 mounting fra...
Страница 14: ...to the IT rack with the furnished cage nuts and screws Figure 2 Mounting the Module Mounting Assembly List 9 19 23 24 with P N SXK2310021 1 Mounting Rail Kit All Lists with P N 562821 Mounting Rail Ki...
Страница 15: ...les can be shipped pre installed in a module mounting assembly using the Open Compute Rack shipping support bracket BBU MODULES CANNOT BE SHIPPED INSTALLED IN A MODULE MOUNTING ASSEMBLY REMOVE SHIPPIN...
Страница 16: ...Vertiv NetXtend 12 VDC Bulk Output Power System Installation and User Manual UM588706000 Rev H 14 Figure 4 Installing P N 561578 Shipping Support Bracket...
Страница 17: ...unding requirements refer to the current edition of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC applicable local co...
Страница 18: ...n module mounting assemblies all module mounting assemblies are on one DC bus and are controlled by a single SCC controller A common CAN bus is shared across all module mounting assemblies and all rec...
Страница 19: ...2 3 9 11 12 13 19 23 24 33 11 mm 0 433 Clearance Holes on 25 4 mm 1 Centers List 4 5 6 7 8 14 15 16 17 18 21 22 31 32 7 10 mm x 10 3 mm 0 281 x 0 406 Slots on 25 4 mm 1 Centers Customer must order or...
Страница 20: ...r Manual UM588706000 Rev H 18 External Alarm Reference Monitoring and Control Connections External Alarm Reference Monitoring and Control Connection Points Locations Refer to Figure 7 Figure 7 Externa...
Страница 21: ...of one 1 main module mounting assembly and up to two 2 expansion module mounting assemblies or all main module mounting assemblies In installations with one main module mounting assembly and up to two...
Страница 22: ...em Interconnection Diagram Rear Main Module Mounting Assembly Rear Expansion Module Mounting Assembly Termination Resistor Cable P N 557463 CAN Bus Cable P N 557463 CAN Bus Cable P N 557553 Power Fail...
Страница 23: ...Manual UM588706000 Rev H 21 AC Input and AC Input Equipment Grounding Connections to Module Mounting Assembly s DANGER Adhere to the Important Safety Instructions presented at the front of this docume...
Страница 24: ...r clarity only AC Input Connections 588706000 List 1 11 Nominal 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz Single Phase 3 Feeds per Module Mounting Assembly 1 Feed per 3 Module Positions AC Feed 3 Positions...
Страница 25: ...9 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz Three Phase L1 L2 Position 7 L2 L3 Position 8 L1 L3 Position 9 AC Feed 2 Positions 4 6 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz Three Phase L1 L2 Position 4 L2 L3 Pos...
Страница 26: ...VAC 415 VAC or 277 VAC 480 VAC 4 Wire PE 50 Hz 60 Hz L1 N Position 7 L2 N Position 8 L3 N Position 9 AC Feed 2 Positions 4 6 240 VAC 415 VAC or 277 VAC 480 VAC 4 Wire PE 50 Hz 60 Hz L1 N Position 4 L...
Страница 27: ...Mounting Assembly AC Input Connections 588706000 List 4 14 Nominal 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz Single Phase 3 Feeds per Module Mounting Assembly 1 Feed per 3 Module Positions Front Main Module...
Страница 28: ...ure 13 AC Input Connections to a 588706000 List 5 15 Module Mounting Assembly AC Input Connections 588706000 List 5 15 Nominal 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz 3 Phase 1 Feed per Module Mounting As...
Страница 29: ...Input Connections to a 588706000 List 6 16 Module Mounting Assembly AC Input Connections 588706000 List 6 16 Nominal 240 VAC 415 VAC or 277 VAC 480 VAC 4 Wire PE 50 Hz 60 Hz 1 Feed per Module Mounting...
Страница 30: ...f AC input protection devices Figure 15 AC Input Connections to a 588706000 List 7 17 Module Mounting Assembly AC Input Connections 588706000 List 7 17 Nominal 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz 3 Ph...
Страница 31: ...protection devices Figure 16 AC Input Connections to a 588706000 List 8 18 Module Mounting Assembly AC Input Connections 588706000 List 8 18 Nominal 240 VAC 415 VAC or 277 VAC 480 VAC 4 Wire PE 50 Hz...
Страница 32: ...AC 240 VAC 50 Hz 60 Hz 3 Phase 1 Feed per Module Mounting Assembly 1 Feed per 9 Module Positions Front Main Module Mounting Assembly Shown Expansion Module Mounting Assembly Similar Rear Main Module M...
Страница 33: ...88706000 List 21 31 Nominal 200 VAC 208 VAC 240 VAC 50 Hz 60 Hz 3 Phase 1 Feed per Module Mounting Assembly 1 Feed per 9 Module Positions Rear Main Module Mounting Assembly Shown Expansion Module Moun...
Страница 34: ...line cord and plug Refer to Figure 19 for wiring details CAUTION AC input sized for module mounting assembly population of rectifier and BBU modules as shown in Figure 19 DO NOT populate slots in any...
Страница 35: ...on 2 5 L1 L3 Position 3 6 AC Feed 2 Positions 7 8 9 208 VAC 50 Hz 60 Hz Three Phase Y L1 L2 Position 7 L2 L3 Position 8 L1 L3 Position 9 NEMA L21 30 Twist Lock Plug 30 AMP NEMA L21 30 Twist Lock Plug...
Страница 36: ...UM588706000 Rev H 34 Connections to List 24 Module Mounting Assembly Spec No 588706000 List 24 Module Mounting Assembly provides an AC input line cord and plug Refer to Figure 21 for wiring details Fi...
Страница 37: ...g Assembly AC Input Connections 588706000 List 25 35 Nominal 230 VAC 400 VAC or 240 VAC 415 VAC 4 Wire PE 1 Feed per Module Mounting Assembly Front Main Module Mounting Assembly Shown Expansion Module...
Страница 38: ...ectifier modules and BBU modules as directed in the Initially Starting the System procedure starting on page 37 For SCC controller installation instructions refer to SCC Controller Instructions UM1M52...
Страница 39: ...3 24 Initially Starting the System Procedure 1 Apply AC input power to the system by closing ALL external AC disconnects or protective devices that supply AC power to the module mounting assembly s 1...
Страница 40: ...Verify all rectifier modules BBU modules and the SCC controller are fully seated latched and the latch handle screws secured 7 Verify there are no external alarms and the local indicators are normal...
Страница 41: ...roller When the load exceeds this current limit the BBU s will provide power as needed Expected Number of Rectifiers and BBU s You can set the number of rectifiers and BBU s expected to be in the syst...
Страница 42: ...ENCED IN Check ventilation openings for obstructions such as dust papers manuals etc Inspect and tighten all installer s connections Making Electrical Connections section of this document BBU Battery...
Страница 43: ...n page 41 and Replacement Procedures on page 41 Replacement Information When a trouble symptom is localized to a faulty rectifier module BBU module or SCC controller that particular device should be r...
Страница 44: ...UM582127000100 11AD1209MU RH 06 17...