Sample Signal: This is the monitor unit sample signal which is associated to the alarm signal. This
signal is used to provide a present value (<monval>) for the TL1 signal (e.g., voltage or temperature
reading). This value is used for TL1 commands and reports.
•
Alarm Signal: This is the alarm signal whose status is being monitored and reported.
•
Setting Signal: This is the monitor unit setting signal which is associated to the alarm signal. This
signal is used to provide the threshold (<thlev>) that has been exceeded to generate the alarm
causing the change in state of the TL1 signal. This value is used for TL1 reports. This field is only
used for alarms associated sample signals which are decimal or integer values (e.g., float, unsigned).
It does not apply to signals with enumerated or digital (binary) values.
•
Condition Type (20 characters maximum): This is the TL1 text designating the condition
corresponding to the alarm. Valid values for this parameter can contain only alphanumeric
characters. TL1 uses specific values for this parameter. Refer to TA-NWT-001360 Tables 5-1
through 5-4.
•
Condition Description (32 characters maximum): This is a detailed text description or
instructions relating to the alarm. Valid values for this parameter can contain only alphanumeric
characters. May also be used to describe any action to be taken as a result of the condition.
•
Notification Code: This is the TL1 notification code for the associated alarm. It should mirror the
alarm severity. Values are CR (critical), MJ, (Major), OB (Observation), NA (Non-alarmed), and NR
(Non-reporting).
-
CR - Critical Alarm
-
MJ - Major Alarm
-
OB - Observation Alarm
-
NA - Not Alarmed
-
NR - Not Reported When Event Occurs
•
Service Effect Code: This is the TL1 service effect code for this alarm. Values are SA (service
affecting) and NSA (Non-Service Affecting).
-
SA = service-affecting condition, immediate action required
-
NSA = nonservice-affecting condition, action required
•
Monitor Value Format (I or D): This specifies the format of the monitored value (monval). Values
are integer (I) and decimal (D).
•
Monitor Type (10 characters maximum): This is the type of parameter being monitored. It should
indicate the units of measurement of the sample signal. This field is only used for sample signals
that are decimal or integer values (e.g., float, unsigned) and does not apply to signals with
enumerated or digital (binary) values. Only alpha characters can be entered for this parameter. TL1
uses specific values for this parameter. Refer to TA-NWT-001360 Table 6-1.
5.
Click the Submit button.
6.
Repeat these steps for other signals to be added to the AID group and to assign signals to other AID
groups.
Содержание NetSure M832DNA
Страница 97: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 97 Figure 62 Restore Factory Defaults ...
Страница 107: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 107 3 The monitor unit restarts Figure 74 Restart ...
Страница 175: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 175 This page is intentionally blank ...
Страница 176: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M832DNA RC 11 19 ...