Vertiv
|
NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
155
Samples
TL1 Message Samples
These samples use the system identifier (<tid>): Lorain.
Autonomous Message on Connect
When the Telnet connection is established, the monitor unit will provide the active alarms in an autonomous
message. In this example, there are two alarms.
Lorain 15-09-24 13:47:00
*C 1 REPT ALM EQPT
"PowerSystem:CR,Alarm,SA,09-24,13-45-31,,,1,,1-MIN:\"CAN Communication Failure\","
"PowerSystem:CR,Alarm,SA,09-23,13-39-43,,,1,,1-DAY:\"SPD\","
;
<
Activate User
The ACT-USER request (example: ACT-USER::drw:51::1_2345; for username drw with password 1_2345) can be
used to log in. The monitor unit will not respond to requests unless a user is logged in (or the monitor unit is
configured with auto-login). The monitor unit responds with this message:
Lorain 15-09-24 15:29:14
M 51 COMPLD
/* This is a private computer system.
Unauthorized access may result in criminal prosecution */
;
<
Cancel User
The CANC-USER request (example: CANC-USER:Lorain:drw:16; for username drw) can be used to log-out the
current user. The monitor unit responds with this message:
Lorain 15-09-25 08:18:04
M 16 COMPLD
;
<
Retrieve Header
The RTRV-HDR request (example: RTRV-HDR:::20;) can be used to ‘ping’ the monitor unit to confirm that there
is a connection established. The monitor unit responds with this message:
Lorain 15-09-25 08:17:57
M 20 COMPLD
;
<
Retrieve Equipment
The RTRV-EQPT request (example: RTRV-EQPT:Lorain:SYSTEM:40;) can be used to get information about the
monitor unit. The monitor unit responds with this message:
Lorain 15-09-25 08:17:55
M 40 COMPLD
"SYSTEM:M830B::SWVER=1.00,CURSWVER=1.1.41T04,:IS-NR,"
;
<
The monitor unit type is M830B. The configuration is version 1.00. The software version is 1.1.41T04.
Содержание NetSure M832DNA
Страница 97: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 97 Figure 62 Restore Factory Defaults ...
Страница 107: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 107 3 The monitor unit restarts Figure 74 Restart ...
Страница 175: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 175 This page is intentionally blank ...
Страница 176: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M832DNA RC 11 19 ...