DESCRIPTION OF LOCAL DISPLAY MENUS
PROGRAMMABLE PARAMETERS
The following are descriptions of the programmable parameters presented in the local display menus.
Settings Menu
Bay Settings Sub-Menu
•
Capacity: Enter the bay’s capacity.
•
High Curr Lmt1: Enter the bay’s high current 1 alarm setpoint. Enter the percentage value of the
"capacity" for alarm.
•
High Curr Lmt2: Enter the bay’s high current 2 alarm setpoint. Enter the percentage value of the
"capacity" for alarm.
•
Num of Panels: Enter the number of panels installed in the bay.
•
Clear Datas: Clears the data stored for the bay.
Distribution Panel Settings Sub-Menu
Select a distribution panel from the panels listed in the menu.
•
Panel Exists: Select “Used” or “Not Used”.
•
Panel Type: Select “Standard” or “Advanced”.
•
Num of Elements: Enter the number of distribution devices that are installed in the distribution panel.
•
Feed ID: Assigned which input feed is connected to the distribution panel. Note: Program the "Feed ID"
for panels starting from panels at the top, to the panels at the bottom.
•
Clear Datas: Clears the data stored for the panel.
•
Distribution Device (Advanced Panels Only): Select a distribution device from the distribution
devices listed in the menu.
-
Device Exists: Select “Used” or “Not Used”.
-
Capacity: Enter the distribution device’s capacity.
-
High Curr Lmt1: Enter the distribution device’s high current 1 alarm setpoint. Enter the percentage
value of the "capacity" for alarm.
-
High Curr Lmt2: Enter the distribution device’s high current 2 alarm setpoint. Enter the
percentage value of the "capacity" for alarm.
-
Breaker Poles: Enter the number of poles the distribution device has.
-
Clear Datas: Clears the data stored for the distribution device.
Содержание NetSure M832DNA
Страница 97: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 97 Figure 62 Restore Factory Defaults ...
Страница 107: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 107 3 The monitor unit restarts Figure 74 Restart ...
Страница 175: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 175 This page is intentionally blank ...
Страница 176: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M832DNA RC 11 19 ...