Vertiv
|
NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
151
alarmStatusChange
The type of alarm change. One of (1) activated (2) deactivated
alarmSeverity
The severity of the alarm. One of (3) warning - OA, lowest level of
alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest
level of alarm severity
alarmDescription
Free-text description of alarm.
alarmType
Alarm type, i.e. an integer specifying the type of alarm.
alarmTrap
An alarm trap is sent when an alarm occurs (activated) or returns to
normal state (deactivated). Alarm traps are logged in alarmTrapTable.
Variables in this trap: * alarmIndex - The unique sequence number of
this alarm trap. * alarmTime - Date and time when event occured
(local time), including timezone if supported by controller. *
alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity -
Integer describing the severity of the alarm. * alarmDescription - Free-
text description of alarm. * alarmType - Integer indicating type of
alarm.
alarmActiveTrap
An alarm trap is sent when an alarm occurs (activated) Variables in
this trap * alarmTime - Date and time when event occured (local
time), including timezone if supported by controller. * alarmSeverity -
Integer describing the severity of the alarm. * alarmDescription - Free-
text description of alarm. * alarmType - Integer indicating type of
alarm.
alarmCeaseTrap
An alarm trap is sent when an alarm returns to normal state (clear,
deactivated). Variables in this trap: * alarmTime - Date and time when
event occured (local time), including timezone if supported by
controller. * alarmSeverity - Integer describing the severity of the
alarm. * alarmDescription - Free-text description of alarm. * alarmType
- Integer indicating type of alarm.
Содержание NetSure M832DNA
Страница 97: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 97 Figure 62 Restore Factory Defaults ...
Страница 107: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 107 3 The monitor unit restarts Figure 74 Restart ...
Страница 175: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 175 This page is intentionally blank ...
Страница 176: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M832DNA RC 11 19 ...