Vertiv
|
NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
112
Data Table
Equipment
NUM
Address
Signal Name
Encoding
Write/Read
Basic
Value
Invalid
Value
Remark
1
215
FeedStatus
Bit 0: Over Voltage1
Alarm
0: Normal 1: Alarm
Bit 2-1: Over Voltage1
Alarm Alarm Level
00: None 01: observer
10: Major 11: Critical
Bit 3: reserve
Bit 4: Over Voltage2
Alarm
0: Normal 1: Limit
Bit 6-5: Over Voltage2
Alarm Alarm Level
00: None 01: observer
10: Major 11: Critical
Bit 7: reserve
Bit 8: Under Voltage1
Alarm
0: Normal 1: Alarm
Bit 10-9: Under Voltage1
Alarm Alarm Level
00: None 01: observer
10: Major 11: Critical
Bit 11: reserve
Bit 12-15: reserve
Read
0
0xFFFF
1
216
FeedStatus
Bit 0 :Under Voltage2
Alarm
0: Normal 1:Alarm
Bit 2-1: Under Voltage2
Alarm Alarm Level
00: None 01: observer
10: Major 11: Critical
Bit 3: reserve
Bit 4: Current Hi1 Alarm
0: Normal 1: Limit
Bit 6-5: Current Hi1
Alarm Alarm Level
00: None 01: observer
10: Major 11: Critical
Bit 7: reserve
Bit 8: Current Hi2 Alarm
0: Normal 1: Alarm
Bit 10-9: Current Hi2
Alarm Alarm Level
00: None 01: observer
10: Major 11: Critical
Bit 11: reserve
Bit 12-15: reserve
Содержание NetSure M832DNA
Страница 97: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 97 Figure 62 Restore Factory Defaults ...
Страница 107: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 107 3 The monitor unit restarts Figure 74 Restart ...
Страница 175: ...Vertiv NetSure Monitor Unit User Manual UM1M832DNA Rev C 175 This page is intentionally blank ...
Страница 176: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M832DNA RC 11 19 ...