Vertiv™ NetSure™ HVT F02 CK1 Power System User Manual
37
Table 3.6 Description of the system parameter setting
Parameter Name
Setting Range
Default
Description
Lang
Chinese, English
English
Set it according to your requirements
Tzone
/
/
Set it according to the actual instance
Date
2000 ~ 2099
/
Set the time according to the current actual time, regardless of whether it is a
leap year or not
Time
/
/
Set the time according to the current actual time
485 Baud
38400
19200
9600
4800
2400
1200
19200
Set it according to your requirements
232 Baud
38400
19200
9600
4800
2400
1200
9600
Set it according to your requirements
232 Addr
1 ~ 254
1
Set it according to your requirements
Reset Paras
Y, N
N
Whether resetting the parameter to the default
User PWD
-
-
The password can be 6 digits long at most. If it is shorter than 6 digits, end it
with space key
ComDownLoad
Y, N
N
When the serial port is needed to upgrade the program or configure files,
enter serial port download mode first
Sys Type
240V DC system
336V DC system
380V AC system
ATS AC system
240V DC system
Set it according to your requirements, 400V system needs to be changed to
336V DC system
NOTE!
Check the ‘System Type’ in the ‘System settings’ screen of the distribution controller, make sure that the system
type is 336V DC system.
3.2
Description of Temperature Acquisition
The DC distribution cabinet can be connected to the temperature sensor. The temperature sensor connected to the DC
distribution cabinet can collect temperature, and the DC distribution LCD will directly display the temperature, then report it to
the controller of the power system.
The same DC distribution cabinet can connect multiple temperature sensors, but only takes the first route (if effective) as battery
temperature. The controller only takes this route for temperature compensation; you do not need to perform settings. If a set of
power system contains has multiple DC distribution cabinets, and each equipment connects with a temperature sensor, then the
controller will perform temperature compensation according to the highest temperature sent from each equipment.
DC distribution cabinet
The J16 and J17 interfaces on the monitoring board of the DC distribution cabinet can collect temperature, and the collected
temperature will display on its own distribution LCDs, with corresponding numbers for temperature 1 and temperature 2. For the
first DC distribution cabinet temperature, it will display ‘temperature 1, temperature 2’ under ‘HDU1’ corresponding to the
controller of the main rectifier cabinet. Temperature 1 (default) is the battery temperature, and the controller will perform
temperature compensation according to temperature 1. Temperature 2 is ambient temperature by default. If you wish to use
these two temperature ports, set them to ‘Enable’ in the controller by referring to
M822E Controller User Manual
.