Vertiv™ NetSure™ HVT F02 CK1 Power System User Manual
31
2. At any sub-menu of the main menu screen, press the ESC key repeatedly to return to the higher-level menu, and ultimately
return to the main menu screen.
Distribution parameter setting
All the distribution parameters are set on the LCD screen of the system main controller, except the address of AC distribution
screen. See 2.3 Power-on for specific settings.
Settings screen
The system settings screen is used to set the time, date and other parameters of the controller, the setting method is as follows:
1. At the Settings screen, press
▲
or
▼
to select the ‘Sys set’ menu. Then press the ENT key to confirm, as shown in Figure 3.5.
Figure 3.5
System settings
2. Press
▲
or
▼
to select the parameter you need, and press
◄
or
►
to select the parameter value. Then press the ENT key to
confirm. The controller will automatically save the setting value.
3.1.3
LCD Operation of DC Distribution Cabinet
The following LCD screens will be mentioned in this chapter for many times. This section is a centralized introduction about the
contents and access methods of these LCD screens.
System information screen
When the controller is powered on, the language selection interface will appear, and the default language is Chinese. If you need
English interface, press
▲
or
▼
for language selection and then press the ENT key to confirm. Then the inside of the controller is
initialized. After the initialization, the first system information page will appear in Figure 3.6.
The system information screen displays the main information. The first system information screen has 7-level contrast (the
contrast can be adjusted only in the first system information screen), you can press
◄
or
►
to adjust the LCD contrast.
Figure 3.6
First system information screen
System: Alarm
2011-12-14
267.1V 100A
Insul: Normal
1. The first row displays the date and time alternately.
2. At the main menu screen, press the ESC key to return to the first system information screen.
3. If no operation is conducted on the controller keypad for 8 minutes, the LCD screen will automatically return to the first system
information screen. The time of that return will be recorded automatically, and can be queried through the host.