Chapter 3 Installation 27
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Step 5: fix the cabinet
After the cabinet is in position, make some horizontal and vertical adjustments. Insert some iron pieces under the
lower edge and corner of the cabinet to adjust the vertical obliquity of the cabinet within 5 degrees. Finally, screw
down the tap bolt with plain washer and spring washer into the expansive pipe, and tighten it with wrench. The
cabinet fixation is illustrated in Figure 3-2.
Tap bolt
Plain washer
Cabinet base
Ground
Spring washer
Expansive pipe
Figure 3-2 Fixing cabinet with tap bolt
3.1.2 Installation On Supporting Rack
If antistatic floor is laid in the equipment room, a supporting rack should be made according to the height of the
antistatic floor.
Step 1: place cabinet in position
Install the supporting rack on the floor as shown in Figure 3-3. The installation steps are the same as the first three
steps in 3.1.1 Installation On The Floor.
Expansive pipe finished
Floor
Expansive pipe
Bolt
Spring washer
Plain washer
Figure 3-3 Installing supporting rack