84 Appendix 1 Technical Parameter
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Parameter
Category
Parameter
Description
Mechnical
Weight (kg)
Rectifier cabinet (not including rectifier)
Rack1000-7
≤ 140
Rack2000-7
≤ 180
Controller M831D
≤ 2
Rectifier R48-5800A, R48-5800e
≤ 8
Table 2 Technical parameters of AC distribution c abinet
Parameter
Category
Parameter
Description
Environmental
Operating temperature
-5°C ~ 40°C
Storage temperature
-40°C ~ 70°C
Relative humidity
5%RH ~ 95%RH
Altitude
≤ 2000m (derating is necessary above 2000m)
Other
No conductive dust or erosive gases. No possibility of explosion
AC input
AC input system
TN-C, TN-S, TN-C-S and TT formats with three- phase four- wire or three- phase five-
wire styles
Rated input phase
voltage
380Vac
Input voltage range
260Vac ~ 530Vac (error is 5Vac)
Input AC voltage
frequency
45Hz ~ 65Hz
45Hz ~ 55Hz (PD380/630AFA-7-Y4)
AC output
Distribution parameters
PD380/400AFH-7-Y2:
6-route 3-phase output, 6-route single phase output, output total capacity not exceeding
400A:
160A/3P × 4, 63A/3P × 1, 32A/3P × 1, 32A/1P × 3, 20A/1P × 3
PD380/630AFH-7-Y3:
8-route 3-phase output, 6-route single phase output, output total capacity not exceeding
630A:
160A/3P × 6, 63A/3P × 1, 32A/3P × 1, 32A/1P × 3, 20A/1P × 3
PD380/630AFA-7-Y4:
8-route 3-phase output, 6-route single phase output, output total capacity not exceeding
600A:
160A/3P × 6, 63A/3P × 1, 32A/3P × 1, 32A/1P × 3, 20A/1P × 3
PD380/630AFH-7/YF: configuration in accordance with customer requirement
(
If the
input switch using MCB, shall not exceed the total capacity of the Cabinet input of MCB
80%)
AC input alarm
and protection
AC input overfrequency
alarm point
Default: 55Hz, configurable through controller
AC input underfrequency
alarm point
Default: 45Hz, configurable through controller
AC input overvoltage
alarm point
Default: 535Vac ± 10Vac (line voltage), not configurable through controller, 10Vac
hysteresis
AC input undervoltage
alarm point
Default: 485Vac ± 10Vac (line voltage), configurable through controller, 10Vac hysteresis
ACinput undervoltage
protection point
Default: 255Vac ± 10Vac (line voltage), not configurable through controller, 15Vac
hysteresis
AC input phase loss
alarm point
Default: 120 ± 10Vac (phase voltage), configurable through controller, 10Vac hysteresis
Overtemperature alarm
point
Default: 50°C, configurable through controller, 2°C hysteresis
EMC
Conducted emission
Class A EN300386
Radiated emission
Immunity to ESD
Level 3 EN/IEC 61000-4-2
Immunity to EFT
Level 4 EN/IEC 61000-4-4
Surge
Level 4 EN/IEC 61000-4-5
Immunity to radiation
Level 2 EN/IEC 61000-4-3
Immunity to conduction
Level 2 EN/IEC61000-4-6