Chapter 4 Testing 53
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Note
The defaults parameter in controller of the system is: ‘LDU mode: NO’, not to change it.
Setting DIP switches of DC distribution cabinet
Distribution cabinet address, communication speed and temperature sensor selection select the desired set by dip
switches on the monitor panel. DIP switch is shown in Figure 4-1.
Bits 1 to 5 are used to set the addresses of the AC distribution cabinets. Position
‘ON’ represents ‘0’, and ‘OFF’
represents
‘1’. The setting explanation of bits 1 to 5 is given in Table 4-4.
Table 4-4 Setting DIP switches of DC distribution cabinet
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Corresponding address in the controller
0
0
0
1
0
72
1
0
0
1
0
73
0
1
0
1
0
74
1
1
0
1
0
75
0
0
1
1
0
76
1
0
1
1
0
77
0
1
1
1
0
78
1
1
1
1
0
79
0
0
0
1
1
88
1
0
0
1
1
89
0
1
0
1
1
90
1
1
0
1
1
91
Note
Address of the AC distribution cabinet default setting from factory is 72, if there are multiple AC screens, set the cabinets address
to 72, 73,…,91.
The setting explanation of bits 6 to 8 is given in Table 4-2.
4.3.2 Setting Basic Parameters For Controller
To put the system into service, system setting must be done through the controller, battery group number, battery
nominal capacity, charge current limit and other function requirements according to the actual system configuration.
Otherwise, the system information display and output control cannot function normally.
1. At the default LCD screen (if stay in other screen, press ESC will exit to the default screen) of the controller in AC
distribution cabinet, press ESC to enter the product information screen, as shown in Figure 4-3, check whether the
‘Address’ is within the range of Table 4-1. If the address is out of the range in Table 4-1 or there are two or above AC
screens set to the same address, then reset the address according to
4.3.1 Setting DIP Switch
.
Model: LargeDU
Software version:
V1.08
Address: 64
Figure 4-3 AC screen address
2. At the default LCD screen of DC distribution cabinet, press ESC to enter the product information screen (see
Figure 4-4). Check whether the
‘Address’ is within the range of Table 4-4. If the address is out of the range in Table
4-4 or there are two or above AC screens set to the same address, then reset the address according to
4.3.1 Setting
DIP Switch
.
Model: LargeDU
Software version:
V1.08
Address: 72
Figure 4-4 DC screen address