Chapter 3 Installation 39
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
A
DC positive busbar
Positive load cable
Spring washer
Plain washer
A amplification
Bolt
Figure 3-20 Connecting positive load cable
3.2.6 Connecting Battery Cables
The connection of battery cables in DC distribution cabinet is described below.
The procedures of connecting battery cables are as follows:
1. Route and number the cables of the 2 batteries and mark their polarities.
2. Connect one end of the negative cable to the output terminal of the battery fuse and one end of the positive cable
to the positive copper bar of the DC distribution cabinet. Add cable lugs to the other end of the positive and negative
cables, bind the cable lugs with insulating tape, and put them beside the battery. Connect the cables to the battery
when the DC distribution is to be initially tested, as shown in Figure 3-21.
Note
The battery negative cables should be connected to the two battery fuses, not the single one.
电池熔断器
电池负极电缆
电池负极电缆
Negative
battery cable
Negative
battery cable
Battery fuse
Battery input cable
Bolt
Plain washer
Spring washer
Nut
Battery busbar (-)
Cable connection finished
Figure 3-21 Battery cable connection in DC cabinet