62 Chapter 4 Testing
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
User can view the IP address: Main menu
——
>
Settings (password:1)
——
>
Communication Parameter, and then
press the
ENT
key.
Figure 4-24 Login the controller
10. In the Web Interface, after entering a valid
User Name
and
Password
and clicking LOGIN, the "Homepage"
window opens, as shown in Figure 4-25.
Figure 4-25 M831D Homepage
11. Check whether all parameters in Figure 4-25 are correct.
12. Control the boost/float and rectifier switch, check whether the control function is correct.
13. Simulate fault alarms on the power system, and then check whether corresponding alarms are displayed in the
homepage.