Figure 3.3 Convert the Liebert PSI XR for rack installation
WARNING! Risk of top-heavy unit falling over. May cause equipment damage, personal injury or
death.Placing heavy equipment near the top of a rack may increase the risk of tipping. Place the
UPS or battery cabinet, if one is being used, in the bottom of the rack.
CAUTION: Risk of strain from lifting heavy equipment. May cause personal injury.Lifting
equipment into rack may be a two-person job, depending on weight of equipment.
NOTICE
When rack-mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails on
each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to
move the UPS into and out of the rack.
3.4 Orient Display for Installation
The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations.
To set the display for your installation, pull out on the display and rotate it until it is oriented correctly,
then press it into the UPS until it is seated.
Vertiv
| Liebert® PSI XR™ User Manual |
11
Содержание Liebert PSI XR 1000
Страница 1: ...Liebert PSI XR 1000 1500 2200 3000 120VAC User Manual...
Страница 6: ...Vertiv Liebert PSI XR User Manual 2 This page intentionally left blank...
Страница 8: ...Vertiv Liebert PSI XR User Manual 4 This page intentionally left blank...
Страница 10: ...Figure 1 3 2200 and 3000VA rear view Vertiv Liebert PSI XR User Manual 6...
Страница 12: ...Vertiv Liebert PSI XR User Manual 8 This page intentionally left blank...
Страница 26: ...Vertiv Liebert PSI XR User Manual 22 This page intentionally left blank...
Страница 30: ...Figure 7 1 Battery replacement Vertiv Liebert PSI XR User Manual 26...
Страница 34: ...Vertiv Liebert PSI XR User Manual 30 This page intentionally left blank...
Страница 36: ...Vertiv Liebert PSI XR User Manual 32 This page intentionally left blank...
Страница 37: ......