7 BATTERY MAINTENANCE
7.1 Battery Charging, Storage
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design
life. The Liebert PSI XR continuously charges the batteries when connected to the mains supply, even
while the UPS is switched Off.
If the Liebert PSI XR will be stored for an extended period, Liebert recommends connecting the UPS to
input power for at least 8 hours every four to six months to keep the batteries charged.
7.2 Internal Battery Replacement Procedure
NOTICE
This UPS is equipped with internal batteries that the user can replace without shutting down
the UPS or connected loads (hot swappable). Caution must be exercised when replacing the
batteries because the load is unprotected from power fluctuations and power failures.
To replace the batteries:
1. Remove the two screws on the left side of the front bezel.
2. Pull the front bezel off the UPS.
3. Remove the two screws on the battery bracket.
4. Remove the screw on the battery connectors holder.
5. Disconnect the two slotted red/gray and black battery connectors.
6. Grasp the battery pack assembly by the handle and pull it out of the front of the UPS.
7. Unpack the new battery assembly, taking care not to destroy the packing.
8. Compare the new and old battery assemblies to make sure they are the same. If so, proceed
with replacement. If they are different, STOP and contact your local dealer, Vertiv
representative or Liebert Applications.
9. Slide the new battery pack into the UPS.
10. Reattach the battery bracket with the two screws.
11. Reconnect the slotted red/gray and black battery connectors.
12. Reinsert the screw on the battery connectors holder.
13. Reattach the front bezel.
Vertiv
| Liebert® PSI XR™ User Manual |
25
Содержание Liebert PSI XR 1000
Страница 1: ...Liebert PSI XR 1000 1500 2200 3000 120VAC User Manual...
Страница 6: ...Vertiv Liebert PSI XR User Manual 2 This page intentionally left blank...
Страница 8: ...Vertiv Liebert PSI XR User Manual 4 This page intentionally left blank...
Страница 10: ...Figure 1 3 2200 and 3000VA rear view Vertiv Liebert PSI XR User Manual 6...
Страница 12: ...Vertiv Liebert PSI XR User Manual 8 This page intentionally left blank...
Страница 26: ...Vertiv Liebert PSI XR User Manual 22 This page intentionally left blank...
Страница 30: ...Figure 7 1 Battery replacement Vertiv Liebert PSI XR User Manual 26...
Страница 34: ...Vertiv Liebert PSI XR User Manual 30 This page intentionally left blank...
Страница 36: ...Vertiv Liebert PSI XR User Manual 32 This page intentionally left blank...
Страница 37: ......