ELECTROMAGNETIC COMPATIBILITY—The Liebert APS complies with the limits of Category C2,
pursuant to IEC/EN/AS 62040-2, and for a Class A digital device, pursuant to Part 15 of FCC rules.
Operation is subject to the following conditions:
•
The output cables must be no longer than 10 m (32 ft).
•
This device may not cause harmful interference.
•
This device must accept any interference received, including interference that may cause
undesired operation. Operating this device in a residential area is likely to cause harmful
interference that users must correct at their own expense.
The Liebert APS complies with the requirements of EMC Directive 2004/108/EC and the published
technical standards. Continued compliance requires installation in accordance with these instructions
and use of accessories approved by Vertiv™.
Operate the unit in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F).
Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
Do not continue to use the Liebert APS if the front panel indications are not in accordance with these
operating instructions or the performance alters in use. Refer all faults to your Vertiv™ representative or
Technical Support.
Servicing of batteries must be performed or supervised by properly-trained and qualified personnel
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the
batteries. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal
requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the Liebert APS,
for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half-wave
rectification.
Storing magnetic media on top of the Liebert APS may result in data loss or corruption.
Turn Off and isolate the Liebert APS before cleaning it. Use only a soft cloth, never liquid or aerosol
cleaners.
Vertiv
| Liebert® APS™ Installer/User Guide |
8
Содержание Liebert APS series
Страница 1: ...Liebert APS 5 20 kVA Modular UPS Installer User Guide...
Страница 6: ...Vertiv Liebert APS Installer User Guide 6...
Страница 10: ...Vertiv Liebert APS Installer User Guide 10 This page intentionally left blank...
Страница 50: ...Vertiv Liebert APS Installer User Guide 50 This page intentionally left blank...
Страница 76: ...Vertiv Liebert APS Installer User Guide 76 This page intentionally left blank...
Страница 80: ...Vertiv Liebert APS Installer User Guide 80 This page intentionally left blank...
Страница 109: ......