MENU
NAME
DATA ITEM
DATA DESCRIPTION
Redundant
Alarm Mode
Allows alarm to be generated when the system loses redundant power module
Settings
(continued)
Communication
Address
Sets the UPS device address. This setting is only for the network card communication of newly emerging market.
Air Filter
Reminder
Set the reminder period of checking dust-proof filter
Air Filter Type
Standard: Use this setting if air filter is not installed.
Fine Dust: Use this setting if air filter is installed.
IT System
Compatibility
Enabled - Neutral back-feed relay will open on battery mode
Disabled (Default) - Neutral back-feed relay is always closed
UPS ID
Users can set the UPS name to facilitate managing the UPS through remote communications
Company
Name
Set the local service company name of the UPS
Contact
Number
Set the local service telephone number of the UPS
Load factory
defaults
Restores the setting items in ‘Settings’ menu to factory values
Battery
settings
Low battery
Warning
Sets the battery low voltage alarm time
Automatic
Battery Test
Interval
Sets the interval for the automatic battery test. Intervals of 8, 12, 16, 20, 26 weeks or Disable are available for
selection. Factory default is 8 weeks.
Auto Batt Test
Start Day
Sets the day of the week for the automatic battery test
Auto Batt Test
Start Time
Sets the time of the day for the automatic battery test
External
Battery AH
Sets the AH capacity of external third party battery system to calculate the battery capacity and estimate the battery
time remaining
Load Factory
Defaults
Restores the setting items in ‘Battery set’ menu to factory values
Language
Language
Options
Provides a selection of seven languages:
Chinese, English, French, Spanish, Italian, Russian and German
Alarms
Current Alarms
Displays the current alarms. See
on page 69 for the UPS alarm list
Records
Historical
Alarms
Displays all historical alarms. See
on page 69 for the UPS alarm list
Table 5.5 Item description of menu window and data window (continued)
Vertiv
| Liebert® APS™ Installer/User Guide |
63
Содержание Liebert APS series
Страница 1: ...Liebert APS 5 20 kVA Modular UPS Installer User Guide...
Страница 6: ...Vertiv Liebert APS Installer User Guide 6...
Страница 10: ...Vertiv Liebert APS Installer User Guide 10 This page intentionally left blank...
Страница 50: ...Vertiv Liebert APS Installer User Guide 50 This page intentionally left blank...
Страница 76: ...Vertiv Liebert APS Installer User Guide 76 This page intentionally left blank...
Страница 80: ...Vertiv Liebert APS Installer User Guide 80 This page intentionally left blank...
Страница 109: ......