2. Connect the cable to the corresponding terminal of the power input and output terminals as
shown in Figure 3.21 below.
3. Using a torque wrench, tighten the screws to 12.43 Nm (110 in-lb).
Figure 3.21 Connection method
Refer to Table 3.6 on page 37 for configuring the output cable. For standard voltages, make the
connections shown in Table 3.8 on the facing page.
SYSTEM VOLTAGE
SYSTEM NOMINAL FREQUENCY
INPUT TERMINAL BLOCK
1
2
PE
200
60
L1
L2
GND
208
60
L1
L2
GND
220
60
L1
L2
GND
230
60
L1
L2
GND
240
60
L1
L2
GND
200
50
L
N
PE
220
50
L
N
PE
230
50
L
N
PE
240
50
L
N
PE
Table 3.7 Key to Figure 3.21 above UPS input wiring
Vertiv
| Liebert® APS™ Installer/User Guide |
40