Vertiv | Liebert EXS 80kVA UPS | User Manual
86
Parallel System and LBS System
•
In a dual-bus
system
, the two UPS systems must have the same power rating, voltage and frequency,
and the load should not exceed the power rating of a UPS module system.
6.5.3. Connecting Power Cables
The power cable of dual-bus system is identical to that of single system. Refer
.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input has a current
leakage protective device, the current leakage protective device must be fitted upstream of the neutral line
input terminal
.
6.5.4. Connecting LBS Cables
Connect the shielded and double-insulated LBS optional cables (5 m, 10 m, and 15 m) between the LBS port of
the two UPS systems as shown in
Figure 6-6 Connection of Typical LBS System (UPS Module)
Содержание EXS 0080kTK16FN01000
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...This page is intentionally left blank...
Страница 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Страница 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Страница 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Страница 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Страница 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Страница 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Страница 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Страница 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Страница 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...