Vertiv | Liebert EXS 80kVA UPS | User Manual
45
Operator Control and Display Panel
Prompt
Meaning
Please open RIB (Inp. Sw.) and BIB (Byp.
Sw.) to turn off UPS
This prompt appears when you turn off UPS.
Turn off UPS? OK or Cancel
This prompt appears when you press the power button, confirm or cancel it
This operation leads to bypass over
current. OK or Cancel
This prompt appears if the bypass can’t supply load during the transfer to
bypass operation or turn off UPS operation when system work in bypass
mode, confirm or cancel it
Reset default password? OK or Cancel
This prompt appears when you press UP and Down and Enter button,
confirm or cancel it
Shutdown in progress
This prompt appears when you turn off UPS
4.4. UPS Alarm Message List
list all the UPS alarm messages based on the ‘Current’ and ‘History’ menus.
Table 4-5 UPS Alarm Message List
Alarm
Meaning
Input Phase Reversed
The AC input phase rotation is reversed
Input Voltage Abnormal
The mains voltage is outside specifications and results in rectifier shutdown
Input Frequency Abnormal
The mains frequency is outside specifications and results in rectifier shutdown
Input Undervoltage
At least one phase main input voltage is within 132 V ~ 176 V, thus the load should be
derated
Excess Auto Retransfers
The load remains on bypass power owing to excessive number of transfers that occurred
within one hour
Excess ECO Auto Transfers
The load remains on inverter power owing to excessive number of transfers that
occurred within one hour
Calibration Shutdown
For tower-type UPS calibration, select the module to be calibrated via the host software.
Shutdown for the modules not to be calibrated, and ’Calibration Shutdown’ alarm
generated
Load Sharing Abnormal
The UPSs in a parallel system are not sharing the load current correctly
Inverter Asynchronous
The output voltage and bypass voltage are misaligned in phase. This alarm resets
automatically once the condition is no longer true
Overvoltage N-GND
Neutral to ground voltage is too high. Check whether the output cable is shorted to the
enclosure or not
Bypass Abnormal
The amplitude or frequency of the bypass voltage exceeds the limit
Bypass Phase Reversed
The phase rotation of the bypass voltage is reversed
Bypass Unable to Trace
The bypass voltage and frequency are outside specifications
Bypass Overcurrent
The bypass current is outside the rated current of 1.1 times
Bypass Not Available
Bypass output disabled under generator mode
Содержание EXS 0080kTK16FN01000
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...This page is intentionally left blank...
Страница 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Страница 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Страница 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Страница 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Страница 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Страница 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Страница 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Страница 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Страница 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...