Vertiv | Liebert EXS 80kVA UPS | User Manual
14
Overview
1.6. Battery Protection
The following battery protection functions are set by the service engineer through the Vertiv setting software.
Battery Low Pre-warning
The battery low pre-warning occurs before the EOD. After this pre-warning, the battery should be able to discharge
with full load for three remaining minutes. The time can be configured from 3 min to 60 min.
EOD Protection
When the battery voltage drops to the EOD voltage, the battery converter automatically shuts down. For VRLA
batteries, the EOD voltage is adjustable from 1.60 V/cell to 1.90 V/cell (VRLA).
BCB Alarm
The BCB alarm occurs when the external BCB opens, if you select the Vertiv BCB (optional).
The external battery connects to the UPS through the BCB. The BCB is manually closed and tripped by the
UPS control circuit.
Содержание EXS 0080kTK16FN01000
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...This page is intentionally left blank...
Страница 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Страница 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Страница 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Страница 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Страница 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Страница 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Страница 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Страница 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Страница 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...