Vertiv | Liebert EXS 80kVA UPS | User Manual
21
Mechanical Installation
2.5. Initial Inspection
Before installing the UPS, carry out the following inspections:
1. Ensure that the UPS equipment room environment meets the environmental requirement specified in the
product technical specifications, especially the ambient temperature, ventilation conditions, and the dust
situations.
2. Unpack the UPS and battery under the guidance of authorized service engineer. Visually inspect if the UPS
and battery have any transportation damage. If there is any damage, report to the carrier immediately.
3. Verify the UPS label and confirm the correctness of the UPS. The UPS label is attached on the rear of the
door. The model, capacity and main parameters of the UPS are marked on the label.
2.6. Environmental Requirements
2.6.1. UPS Room
The UPS should be located in a cool, dry, clean-air indoor environment with adequate ventilation, and should
be located on concrete or other nonflammable and flat surfaces. The ambient environment should be free of
conductive powder (such as metallic powder, sulfide, sulfur dioxide, graphite, carbon fiber, conductive fiber, etc.),
acid mist or other conductive media (strongly ionized substances). The environment specifications should comply
with relevant international standard & specifications and the operating range specified in this manual.
The UPS uses forced cooling by internal fans. Cooling air enters the UPS through the ventilation grills at the
front of the cabinet and exhausted through the ventilation grills at the back of the cabinet. Do not obstruct
the ventilation holes (ventilation grills). The front and rear of the UPS should be kept at a distance at least 200
mm (see
) from the wall to avoid blocking the UPS heat dissipation, thus reducing the UPS internal
temperature and improving the UPS life.
If necessary, install indoor extractor fans to aid cooling-air flow to avoid room temperature buildup. Air filters
(optional) should be used when the UPS is to operate in a dirty environment.
Содержание EXS 0080kTK16FN01000
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...This page is intentionally left blank...
Страница 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Страница 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Страница 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Страница 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Страница 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Страница 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Страница 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Страница 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Страница 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...