RFSDV34 Freestanding Direct Vent Gas Stove
10003550
STEP 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 1”/305 mm). Assemble
sleeve and attach to firestop with #8 sheet metal screws
(supplied). Install firestop assembly. (Fig. 14)
Zero clearance sleeve is only required for
combustible walls.
X
&0
HTTOCENTER
FP1508
Fig. 15
Height to center of wall opening.
ZCS101
Zero Clearance Sleeve
3/11/99 djt
Max. Length
1” (305 mm)
#8 Screws ()
#8 Screws
()
Adjustable
Zero Clearance
Sleeve
#8 Screws
()
Adjustable Zero Clearance Sleeve
ZCS101
Fig. 14
Adjustable zero clearance sleeve.
Firestop
STEP 3
Place stove into position. (Fig. 15) Measure the vertical
height (X) required from the base of the flue collars to the
center of the wall opening.
STEP 4
Apply a bead of high temperature sealant to the inner and
outer flue collars of the stove and using appropriate venting
component(s) attach to stove with three (3) screws. (Fig.
16) Follow with the installation of the inner and outer elbow.
Again secure joints as described on Page 8.
FSDV Step 4b
8-26-02 rjs
FP1509
Bead of Sealant
Fig. 16
Horizontal vent length.
STEP 5
Measure the horizontal length requirement including a
” (51 mm) overlap, ie from the elbow to the outside wall
face plus ” (51 mm) (or the distance required if installing
a second 90° elbow). (Fig. 17)
Always install horizontal venting on a level
plane.
X
FP1510
Fig. 17
Horizontal length to wall.
STEP 6
NOTE: If using charcoal wall plate Pt. #10000257, and
collar Pt. # 52203-CG, put them in place before putting
the pipe sections through the wall.
Use appropriate length of pipe sections - telescopic or fixed
- and install the horizontal vent sections. The sections which
go through the wall are packaged with the starter kit, and
can be cut to suit if necessary. (Fig. 18)
Sealing vent pipe and firestop gaps with high
temperature sealant will restrict cold air being
drawn in around stove.