BLDV7 Series Gas Fireplace
CLEARANCES
CLEARANCES TO COMBUSTIBLES
Figure 4 -
Clearances From The Mantel, Ceiling, and
Side Wall
71” Minimum
Ceiling
13” Min.
From Opening
12” Max.
Depth
6”
Min.
FP2333
BLDV mantel clear
FP2333
45°
1”
2
¹⁄₂
”
3”
5”
1
¹⁄₂
”
6”
3
¹⁄₂
”
4
¹⁄₂
”
FP2334a
BLDV side leg clear
Figure 4a -
Mantel Clearances
Side of Fire-
place Opening
Wall
Combustible
Material Area
FP2334a
Top View
2
¹⁄₄
” Max.
1
¹⁄₂
” Max.
7
¹⁄₂
”
Min.
13”
Min.
12” Max.
FP2904
mantel w eyebrow
Combustible
Breastplate
3/4" Marble
Eyebrow Canopy
Figure 4b -
Mantel Clearance with Eyebrow Canopy
NOTE:
When eyebrow canopy is used, minimum clearance
to combustibles is 21/4" maximum out from fireplace front at
71/2" minimum from opening.
Figure 4b.
When eyebrow is
not used, clearances to combustibles is 12" maximum out
from fireplace front at 13" minimum from opening.
Figure 4
WARNING
Follow these instructions carefully to ensure safe
installation. Failure to follow instructions exactly can
create a fire hazard.
The appliance cannot be installed on a carpet, tile or
other combustible material other than wood flooring. If
installed on carpet or vinyl flooring, the appliance shall
be installed on a metal, wood or noncombustible material
panel extending full width and depth of the appliance.