BLDV7 Series Gas Fireplace

VENTING INSTALLATION 

Step 7

Guide the vent terminations 4” and 7” collard into their 

respective vent pipes. Double check that the vent pipes 

overlap the collars by 2” (51 mm). Secure the termination 

to the wall with screws provided and caulk around the 

wall plate to weatherproof. As an alternative to screwing 

the termination directly to the wall, you may also use ex-

panding plugs or an approved exterior construction ad-

hesive. You may also attach the termination with screws 

through the inner body into the 4” vent pipe, however 

for this method, you must extend the 4” pipe approxi-

mately 6” (152 mm) beyond the outer face of the wall. 

Support horizontal pipes every 36” (914 

mm) with metal pipe straps.

VERTICAL SIDEWALL INSTALLATION - 

FLEX VENT PIPE

 

NOTE:

 The 40” (1016 mm) flex vent is used for 90° bend 

after a straight vertical section (12" min.) then out the 

back wall. 

Figure 20

Follow Steps 1 - 3 on Page 17.

Step 4

Install the four (4) spacer springs on the 4” flex vent pipe. 

When installing the spacer springs  around the 4” pipe, 

stretch the spring to approximately 15” (381 mm), wrap 

the spring around the pipe and interlock the ends of the 

spacer spring approximately 2” (51 mm). Measure 183/4” 

(476 mm) from the end of the pipe. Place the next spring 

5” (127 mm) from the previously installed spring. Place 

the next spring 6” (152 mm) from the last spring. Finally 

place the last spring 12” (305 mm) from the last spring 

installed. 

Figure 19

Step 5

Install the 4” (102 mm) flex vent pipe to the appliance col

-

lar as described on Page 13. Secure the end with the first 

spring 183/4” (476 mm) from the flex pipe end to the unit.

Step 6

Slide the 7” (178 mm) flex vent pipe over the 4” flex vent 

pipe and secure the 7” collar as described on Page 13.

Step 7

Bend the flex pipe horizontal so the bottom of the horizon

-

tal pipe measure 181/2” (470 mm) from the top of the unit 

immediately after the 90° formation. 

Figure 20.

 Be sure to 

follow the 1/2” (13 mm) rise in a 12” (305 mm) horizontal 

run rule.

Step 8

Install the 4” flex then 7” flex to the termination.

12"

(305  mm)

6"

(152 mm)

5"

(127 mm)

18

³⁄₄

"

(476 mm)

FP1474
spacer springs
4/04  djt

4" Flex 

Vent Pipe

Spacer 

Spring

FP1474

Figure 19 - 

Install Spacer Springs

*18

¹⁄₂

(470 mm)

Min.

FP1475
flex 90 bend
4/04  djt

Figure 20 - 

Bend Flex Vent at 

90° so Horizontal 

Portion is 18

1/2

(470 mm) Off Top of 

Unit

FP1475

BELOW GRADE INSTALLATION

When it is not possible to meet the required vent terminal 

clearances of 12” (305 mm) above grade level, a snor-

kel kit is recommended. It allows installation depth down 

to 7” (178 mm) below grade level. The 7” (178 mm) is 

measured from the center of the horizontal vent pipe as it 

penetrates through the wall.

Ensure the sidewall venting clearances are observed. 

If venting system is installed below ground, we rec-

ommend  a  window  well  with  adequate  and  proper 

drainage to be installed around the termination area.

If installing a snorkel, a minimum 24” (610 mm) vertical 

rise is necessary. The maximum horizontal run with the 

24” vertical pipe is 36” (914 mm). This measurement is 

taken from the collar of the fireplace (or transition elbow) 

to the face of the exterior wall. See the Sidewall Venting 

Graph for extended horizontal run if the vertical exceeds 

24” (610 mm).
1.  Establish vent hole through the wall. 

Page 17, Figure 16

*Includes collar height, 

12" straight section and 

bend radius.

Содержание BLDV300N SC7SB

Страница 1: ...service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Thisappliance...

Страница 2: ...allation 26 Check the Gas Type and Pressure 26 Electrical Wiring SCS 26 Junction Box Wiring 27 Command Center Wall Installation 27 Wall Switch Installation 27 Signature Command Wiring Diagram 28 Optio...

Страница 3: ...for future reference IMPORTANT SAFETY INFORMATION This fireplace is a vented product This fireplace must be properly installed by a qualified service person The glass door must be properly seated and...

Страница 4: ...TESTED TO latest edition BLDV300 ANSI Z21 50 CSA 2 22 BLDV400 500 ANSI Z21 88 CSA 2 33 STANDARDS A manufactured home USA only or mobile home OEM installation must conform with the Manufactured Home C...

Страница 5: ...own Hi Lo Knob On Off RS Switch Ignitor FP2073 HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For el...

Страница 6: ...745 mm 317 8 810 mm 317 8 810 mm H 301 16 764 mm 3115 16 811 mm 3515 16 913 mm I 3 76 mm 3 76 mm 3 76 mm J 1 25 mm 1 25 mm 1 25 mm K 99 16 243 mm 113 8 289 mm 113 8 289 mm L 15 16 24 mm 15 16 24 mm 1...

Страница 7: ...for firebox dimensions The framing headers may rest on the top of the firebox standoffs Do not bring headers below top of standoffs NOTE When planning your framing and installation keep in mind that y...

Страница 8: ...due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing Refer to Venting...

Страница 9: ...with Eyebrow Canopy NOTE When eyebrow canopy is used minimum clearance to combustibles is 21 4 maximum out from fireplace front at 71 2 minimum from opening Figure 4b When eyebrow is not used clearanc...

Страница 10: ...costly reconstruction Only noncombustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permi...

Страница 11: ...12 of run towards the termination below 71 2 feet of vertical rise With 71 2 feet or more vertical rise off top of fireplace the horizontal run may run level NEVER run vent piping downward Horizontal...

Страница 12: ...TU h 30kW 36 91cm for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clear...

Страница 13: ...tion caps 2 All mechanical air intakes within 10 1 m of a termination cap must be a minimum of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be...

Страница 14: ...instructions to determine the re lationship between the vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the oute...

Страница 15: ...cal Rise Required Before Horizontal Run FP2338 WARNING Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and...

Страница 16: ...ength is re duced by 36 914 mm Figures 13 14 This does not apply if the 90 elbows are used to increase or redirect a vertical rise Figure 12 3 x 90 Elbows FP1176 Figure 12 Maximum Three 3 90 Elbows pe...

Страница 17: ...oncombustible Walls Hole opening must be 71 2 191 mm in diameter Step 2 Secure firestop to the inside frame center in the 95 8 x 95 8 vent opening Step 3 Place fireplace into position Measure the vert...

Страница 18: ...with the first spring 183 4 476 mm from the flex pipe end to the unit Step 6 Slide the 7 178 mm flex vent pipe over the 4 flex vent pipe and secure the 7 collar as described on Page 13 Step 7 Bend th...

Страница 19: ...e necessary to ex tend vent pipes out as far as the protruding wall face Figure 22 VERTICAL THROUGH THE ROOF APPLICATION This gas fireplace has been approved for Vertical installations up to 40 12 m i...

Страница 20: ...e is below the shingles Figure 29 8 Install appropriate pipe sections until the venting is above the flashing Figure 29 9 Install storm collar and seal around the pipe FP2304 CDV7 top restrictor 3 09...

Страница 21: ...arance Termination Vent Storm Collar Flashing Lowest Discharge Opening Concentric Vent Pipe 1 Minimum Clearance to Combustibles FP1971 Horizontal Overhang Figure 28 Minimum Chimney Clearance Roof Pitc...

Страница 22: ...se the CSA design certified equip ment shutoff valve from your dealer For propane LP connections only the installer must supply an external regulator The external regulator will reduce incoming gas pr...

Страница 23: ...ance Figure 31 CAUTION Use pipe joint sealant that is resistant to liquid petroleum LP gas 3 Minimum FP1978 gas connection Pipe Nipple Cap Figure 31 Gas Connection Tee Joint Approved Flexible Gas Line...

Страница 24: ...ee tabs on top of fireplace 4 Set glass frame aside Each clamp has a quick spring force When reinstalling clamps keep fingers clear CAUTION Glass Frame Safety Screen Barrier Figure 32 Remove Glass Fra...

Страница 25: ...p of facing Hook bottom lip of facing into groove of eyebrow Pull eyebrow forward until it stops Figure 33 4 Insert self tapping screws into tabs on bottom of eye brow and into sides of facing NOTE Ey...

Страница 26: ...he Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are used for back up during power outages 2 The Si...

Страница 27: ...mum by using two 2 SCSWEK cables plugged together Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from the com mand center Attach the connector to the...

Страница 28: ...in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector...

Страница 29: ...installation WARNING Electrical Grounding Instructions This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a prope...

Страница 30: ...n the center turn off unit and let cool After unit cools remove logs If the back holes are clear add more rock wool to the center of the burner Replace logs and check flame again Save left over rock w...

Страница 31: ...TY BARRIER INSTALLATION INSTRUCTIONS 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 40 with the correspond ing slots on the firebox Fig...

Страница 32: ...LOG PLACEMENT 1 Place the rear log 1 in place by sliding it over the rear pins on the right and the left 2 Place the right front log 3 over the burner and grate by matching the hole on the bottom of...

Страница 33: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not...

Страница 34: ...gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will...

Страница 35: ...y Indication for Transmitter X X X X X Child Proof Lock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode...

Страница 36: ...ttent pilot Intermittent Pilot Standing Pilot Temp Shutoff Hold the ON s button 3 seconds when the master switchon the main burner is off RF Remote Receiver On Off Push the RF receiver On Off button o...

Страница 37: ...urn on the main burner with maximum flame height 2 Press the OFF button to decrease flame height The first Function Operation Power Up Flip the master switch to the ON position to power up the system...

Страница 38: ...rom the burner should be visually checked as soon as the heater is installed and periodically during normal operation In normal operation at full rate and after operating for about 15 to 30 minutes th...

Страница 39: ...d Handle glass door with care to avoid striking or scratch ing it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the insi...

Страница 40: ...tion C Check for proper installation and free dom from debris or blockage 2 Glass Soots A Flame impingement on logs A Install log set per the instructions Inspect the injector and air intake area Make...

Страница 41: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 42: ...20306741 42 BLDV7 Series Gas Fireplace TROUBLESHOOTING 4 3 8 7 2 6 743000 BLDV 7 parts 5 FIREBOX COMPONENTS 1...

Страница 43: ...wer w Speed Control 1 BLOTBLDV BLOTBLDV BLOTBLDV 6 SCS Blower w Speed Control Time Delay 1 BLOTBLDVSC BLOTBLDVSC BLOTBLDVSC 8 Firebrick Set Cottage Clay 1 FBBLDV300CC FBBLDV400CC FBBLDV500CC 8 Firebri...

Страница 44: ...20306741 44 BLDV7 Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 743000 BLDV SC parts 1 2 3 4 20 5 6 7 8 9 13 14 15 16 17 12...

Страница 45: ...80D0010 Wire Command Center Control Box 2 feet not shown 1 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 12 A C Adapter 6 volt 1 80D0041 80D0041 80D0041 80D0041 80D0041 80D0041 Fuel Conversion Kits...

Страница 46: ...escription Qty BLDV300 BLDV400 BLDV500 1 Rear Log 1 1 20302139 74D0053 74D0053 2 Right Upper Log 2 1 20302140 74D0054 74D0054 3 Right Front Log 3 1 20302141 74D0055 74D0055 4 Small Twig 4 1 20302142 7...

Страница 47: ...Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 Twist Lock Elbows 45 Elbow for Vertical Horizontal Offset 7TDV45 45 Elbow for Vertical Offsets 8 pack...

Страница 48: ...18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30...

Страница 49: ...4DT 4 4D24 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 4D36 3 6 48 Pipe Length galvanized 46DVA 48 902 4DT 48 4D48 4 6 81 2 Pipe Extension galvanized 46DVA 08A 4DT AJ 4 6 16 Pipe Extension galv...

Страница 50: ...30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 2 Approved Carbon Mon...

Страница 51: ...be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect...

Страница 52: ...This page intentionally left blank...

Страница 53: ...This page intentionally left blank...

Страница 54: ...istique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS FIREPLACE EFFICIENCY PERCENTAGE BLDV300NSC7 60 2 BLDV400NSC7 68 1 BLDV500NSC7 64...

Отзывы: