BLDV7 Series Gas Fireplace

SIGNATURE COMMAND INSTALLATION

Figure 34 - 

Signature Command Valve

FP1909a
signature command valve
alternate view
8/08

Pressure Inlet

Pilot Adjust-

ment Screw

Pressure Outlet

CHECK THE GAS TYPE AND PRESSURE

1.  Check gas type. The gas supply must be the same as 

stated on the appliance’s rating decal. If the gas supply 

is different from the fireplace, 

STOP!

 Do not install the 

appliance. Contact your dealer immediately.

2.  To ease installation, a 24" (610 mm) flex line with manual 

shut-off valve has been provided with on this appliance. 

Install and attach 1/2" gas line onto shut-off valve. 

3. After completing gas line connection, purge air from 

gas line and test all gas joints from the gas meter to the 

fireplace for leaks. Use a solution of 50/50 water and 

soap solution or a gas sniffer. 

4.  To check gas pressures at valve, turn captured screw 

counter clockwise 2 or 3 turns and then place tubing 

to pressure gauge over test point. Turn unit to high.  

Figure 34. 

After taking pressure reading, be sure and 

turn captured screw clockwise firmly to reseal. Do not 

over torque. Check test points for gas leaks.

ELECTRICAL WIRING 

General

1.  This fireplace is equipped with the Signature Control 

valve which operates on 6 volts. The 6 volt DC adapter 

plugs into the fireplace junction box A/C power supply. 

Four (4) “AA” batteries are used for back up during 

power outages.

2.  The Signature Command System can also be operated 

without A/C power. The system can run on four (4) “AA” 

batteries for approximately six (6) months under normal 

use.

3. A/C power must be used to power the A/C module, 

blowers, lights and AUX accessories if used with this 

fireplace.

Optional Accessory Requirements

1.  This  fireplace  may  be  used  with  a  wall  switch,  wall 

mounted thermostat and/or Signature Command wire-

less controls.

2.  The command center control may be mounted on the 

wall with the use of the SCSWEK 15ft. wall mount 

extension kit.

CAUTION

Label all wires before disconnecting when servicing 

controls. Wiring errors can cause improper and 

dangerous operation.

WARNING

Electrical connections should only be performed by a 

qualified, licensed electrician. Main power must be off 

when connecting to main electrical power supply or 

performing service. All wiring shall be in compliance 

with all local, city and state codes. The appliance, when 

installed, must be electrically grounded in accordance 

with local codes or in the absence of local codes, with the 

National Electrical Code ANSI/NFPA 70 (latest edition) 

and Canadian Electrical Code, CSA C22.1.

WARNING

Do not use open flame to check for gas leaks.

Содержание BLDV300N SC7SB

Страница 1: ...service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Thisappliance...

Страница 2: ...allation 26 Check the Gas Type and Pressure 26 Electrical Wiring SCS 26 Junction Box Wiring 27 Command Center Wall Installation 27 Wall Switch Installation 27 Signature Command Wiring Diagram 28 Optio...

Страница 3: ...for future reference IMPORTANT SAFETY INFORMATION This fireplace is a vented product This fireplace must be properly installed by a qualified service person The glass door must be properly seated and...

Страница 4: ...TESTED TO latest edition BLDV300 ANSI Z21 50 CSA 2 22 BLDV400 500 ANSI Z21 88 CSA 2 33 STANDARDS A manufactured home USA only or mobile home OEM installation must conform with the Manufactured Home C...

Страница 5: ...own Hi Lo Knob On Off RS Switch Ignitor FP2073 HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For el...

Страница 6: ...745 mm 317 8 810 mm 317 8 810 mm H 301 16 764 mm 3115 16 811 mm 3515 16 913 mm I 3 76 mm 3 76 mm 3 76 mm J 1 25 mm 1 25 mm 1 25 mm K 99 16 243 mm 113 8 289 mm 113 8 289 mm L 15 16 24 mm 15 16 24 mm 1...

Страница 7: ...for firebox dimensions The framing headers may rest on the top of the firebox standoffs Do not bring headers below top of standoffs NOTE When planning your framing and installation keep in mind that y...

Страница 8: ...due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing Refer to Venting...

Страница 9: ...with Eyebrow Canopy NOTE When eyebrow canopy is used minimum clearance to combustibles is 21 4 maximum out from fireplace front at 71 2 minimum from opening Figure 4b When eyebrow is not used clearanc...

Страница 10: ...costly reconstruction Only noncombustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permi...

Страница 11: ...12 of run towards the termination below 71 2 feet of vertical rise With 71 2 feet or more vertical rise off top of fireplace the horizontal run may run level NEVER run vent piping downward Horizontal...

Страница 12: ...TU h 30kW 36 91cm for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clear...

Страница 13: ...tion caps 2 All mechanical air intakes within 10 1 m of a termination cap must be a minimum of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be...

Страница 14: ...instructions to determine the re lationship between the vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the oute...

Страница 15: ...cal Rise Required Before Horizontal Run FP2338 WARNING Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and...

Страница 16: ...ength is re duced by 36 914 mm Figures 13 14 This does not apply if the 90 elbows are used to increase or redirect a vertical rise Figure 12 3 x 90 Elbows FP1176 Figure 12 Maximum Three 3 90 Elbows pe...

Страница 17: ...oncombustible Walls Hole opening must be 71 2 191 mm in diameter Step 2 Secure firestop to the inside frame center in the 95 8 x 95 8 vent opening Step 3 Place fireplace into position Measure the vert...

Страница 18: ...with the first spring 183 4 476 mm from the flex pipe end to the unit Step 6 Slide the 7 178 mm flex vent pipe over the 4 flex vent pipe and secure the 7 collar as described on Page 13 Step 7 Bend th...

Страница 19: ...e necessary to ex tend vent pipes out as far as the protruding wall face Figure 22 VERTICAL THROUGH THE ROOF APPLICATION This gas fireplace has been approved for Vertical installations up to 40 12 m i...

Страница 20: ...e is below the shingles Figure 29 8 Install appropriate pipe sections until the venting is above the flashing Figure 29 9 Install storm collar and seal around the pipe FP2304 CDV7 top restrictor 3 09...

Страница 21: ...arance Termination Vent Storm Collar Flashing Lowest Discharge Opening Concentric Vent Pipe 1 Minimum Clearance to Combustibles FP1971 Horizontal Overhang Figure 28 Minimum Chimney Clearance Roof Pitc...

Страница 22: ...se the CSA design certified equip ment shutoff valve from your dealer For propane LP connections only the installer must supply an external regulator The external regulator will reduce incoming gas pr...

Страница 23: ...ance Figure 31 CAUTION Use pipe joint sealant that is resistant to liquid petroleum LP gas 3 Minimum FP1978 gas connection Pipe Nipple Cap Figure 31 Gas Connection Tee Joint Approved Flexible Gas Line...

Страница 24: ...ee tabs on top of fireplace 4 Set glass frame aside Each clamp has a quick spring force When reinstalling clamps keep fingers clear CAUTION Glass Frame Safety Screen Barrier Figure 32 Remove Glass Fra...

Страница 25: ...p of facing Hook bottom lip of facing into groove of eyebrow Pull eyebrow forward until it stops Figure 33 4 Insert self tapping screws into tabs on bottom of eye brow and into sides of facing NOTE Ey...

Страница 26: ...he Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are used for back up during power outages 2 The Si...

Страница 27: ...mum by using two 2 SCSWEK cables plugged together Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from the com mand center Attach the connector to the...

Страница 28: ...in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector...

Страница 29: ...installation WARNING Electrical Grounding Instructions This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a prope...

Страница 30: ...n the center turn off unit and let cool After unit cools remove logs If the back holes are clear add more rock wool to the center of the burner Replace logs and check flame again Save left over rock w...

Страница 31: ...TY BARRIER INSTALLATION INSTRUCTIONS 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 40 with the correspond ing slots on the firebox Fig...

Страница 32: ...LOG PLACEMENT 1 Place the rear log 1 in place by sliding it over the rear pins on the right and the left 2 Place the right front log 3 over the burner and grate by matching the hole on the bottom of...

Страница 33: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not...

Страница 34: ...gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will...

Страница 35: ...y Indication for Transmitter X X X X X Child Proof Lock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode...

Страница 36: ...ttent pilot Intermittent Pilot Standing Pilot Temp Shutoff Hold the ON s button 3 seconds when the master switchon the main burner is off RF Remote Receiver On Off Push the RF receiver On Off button o...

Страница 37: ...urn on the main burner with maximum flame height 2 Press the OFF button to decrease flame height The first Function Operation Power Up Flip the master switch to the ON position to power up the system...

Страница 38: ...rom the burner should be visually checked as soon as the heater is installed and periodically during normal operation In normal operation at full rate and after operating for about 15 to 30 minutes th...

Страница 39: ...d Handle glass door with care to avoid striking or scratch ing it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the insi...

Страница 40: ...tion C Check for proper installation and free dom from debris or blockage 2 Glass Soots A Flame impingement on logs A Install log set per the instructions Inspect the injector and air intake area Make...

Страница 41: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 42: ...20306741 42 BLDV7 Series Gas Fireplace TROUBLESHOOTING 4 3 8 7 2 6 743000 BLDV 7 parts 5 FIREBOX COMPONENTS 1...

Страница 43: ...wer w Speed Control 1 BLOTBLDV BLOTBLDV BLOTBLDV 6 SCS Blower w Speed Control Time Delay 1 BLOTBLDVSC BLOTBLDVSC BLOTBLDVSC 8 Firebrick Set Cottage Clay 1 FBBLDV300CC FBBLDV400CC FBBLDV500CC 8 Firebri...

Страница 44: ...20306741 44 BLDV7 Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 743000 BLDV SC parts 1 2 3 4 20 5 6 7 8 9 13 14 15 16 17 12...

Страница 45: ...80D0010 Wire Command Center Control Box 2 feet not shown 1 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 12 A C Adapter 6 volt 1 80D0041 80D0041 80D0041 80D0041 80D0041 80D0041 Fuel Conversion Kits...

Страница 46: ...escription Qty BLDV300 BLDV400 BLDV500 1 Rear Log 1 1 20302139 74D0053 74D0053 2 Right Upper Log 2 1 20302140 74D0054 74D0054 3 Right Front Log 3 1 20302141 74D0055 74D0055 4 Small Twig 4 1 20302142 7...

Страница 47: ...Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 Twist Lock Elbows 45 Elbow for Vertical Horizontal Offset 7TDV45 45 Elbow for Vertical Offsets 8 pack...

Страница 48: ...18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30...

Страница 49: ...4DT 4 4D24 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 4D36 3 6 48 Pipe Length galvanized 46DVA 48 902 4DT 48 4D48 4 6 81 2 Pipe Extension galvanized 46DVA 08A 4DT AJ 4 6 16 Pipe Extension galv...

Страница 50: ...30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 2 Approved Carbon Mon...

Страница 51: ...be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect...

Страница 52: ...This page intentionally left blank...

Страница 53: ...This page intentionally left blank...

Страница 54: ...istique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS FIREPLACE EFFICIENCY PERCENTAGE BLDV300NSC7 60 2 BLDV400NSC7 68 1 BLDV500NSC7 64...

Отзывы: