background image

58

20306747

DVM Series Direct Vent Gas Fireplace

MASSACHUSETTS RESIDENTS ONLY

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any residence with a direct vent product must have a carbon 

monoxide (CO) detector installed in the residence.

Installation of the fireplace or vented gas log in the State of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a 

T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In addition, vent free products may not be installed in a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have a 

T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise 10.8.3 by adding the following additional 

requirements:

(a)  For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 

or in part for residential purposes, including those owned 

or operated by the Commonwealth and where the side wall 

exhaust vent termination is less than seven (7) feet above 

finished grade in the area of the venting, including but not limited 

to decks and porches, the following requirements shall be 

satisfied:

1. 

Installation of carbon monoxide detectors. 

At the time 

of installation of the side wall horizontal vented gas fueled 

equipment, the installing plumber or gas fitter shall observe 

that a hard wired carbon monoxide detector with an alarm and 

battery back-up is installed on the floor level where the gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon monoxide detector with an alarm is installed on each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard wired carbon monoxide detector with alarm and battery 

back-up may be installed on the next adjacent floor level.

 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

2. 

Approved Carbon Monoxide Detectors.

 

Each carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

3. 

Signage.

 A metal or plastic identification plate shall 

be permanently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4. 

Inspection.

 The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment shall not approve 

the installation unless, upon inspection, the inspector observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 

dwelling, building or structure used in whole or in part for 

residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System Provided.

 

When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides 

a venting system design or venting system components with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:

1. Detailed instructions for the installation of the venting 

system design or the venting system components; and

2. A complete parts list for the venting system design or 

venting system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled equipment 

does not provide the parts for venting the flue gases, but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:

1. The referenced "special venting system" instructions 

shall be included with the appliance or equipment installation 

instructions; and

2. The “special venting systems” shall be Product Approved 

by the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all 

venting design

Please read and follow these special requirements

Содержание 500DVMNSC

Страница 1: ...tly located manufactured home USA only or mobile home where not prohibited by local codes This appliance is for use only with the type of gas indicated on the rating plate This appliance is not conver...

Страница 2: ...ugh the Roof Configuration 22 Vertical Through the Roof Installation 23 Installation for Vertical Termination 23 Flat Ceiling Installation 23 Flex Venting Installation 25 5 x 8 Flex Vent Pipe 25 4 x 7...

Страница 3: ...nit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning a...

Страница 4: ...th the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LISTED VENTED GAS FIREPLACE HEATER ANSI Z21 88 2014_CSA 2 33 2014 STANDARDS A manufactured home USA...

Страница 5: ...and System Hi Lo Knob Blower Control On Off RS Switch Ignitor 1 2 Nailing Flange 5 8 Nailing Flange 1 2 Nailing Flange Eyebrow Insulation Board Standoff FP2407 GAS PRESSURES Model Fuel Max Input BTU h...

Страница 6: ...3215 16 837 mm 3815 16 989 mm G 427 16 1079 mm 427 16 1079 mm H 341 2 876 mm 341 2 876 mm I 233 16 589 mm 233 16 589 mm J 345 8 880 mm 345 8 880 mm K 161 8 410 mm 191 8 486 mm L 149 16 370 mm 149 16 3...

Страница 7: ...ur compounds NOTE COLD CLIMATE INSULATION If you live in a cold climate seal all cracks around your appliance and wherever cold air could enter the room with noncombustible material It is especially i...

Страница 8: ...to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section fo...

Страница 9: ...learances MANTEL CLEARANCES NOTE The combustible area above the facing must not protrude more than 1 2 from the facing If it does it is considered a mantel and must meet the mantel requirements listed...

Страница 10: ...cure fireplace Screws Screws Screws Screws Nail Flange Nail Flange Framing FP2411 Insulation Board Do not remove insulation board WARNING FINISHING MATERIAL NOTE Any remote wiring i e remote control w...

Страница 11: ...sket Figure 7 FP1991 remove screws Flue Pipe Cover Flue Pipe Adapter Screws FP1991 4 Remove six 6 screws securing the flue pipe to the back of the intake box and remove the pipe and gasket Figure 8 5...

Страница 12: ...are of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system Installation of any damaged venting component Unauthorized modification of...

Страница 13: ...e top of the flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration If vertical ri...

Страница 14: ...combustible material Maintain proper clearances to all combustible materials NOTICE Treatment of firestops and construction of the chase may vary from building type to building type These instruction...

Страница 15: ...00 BTU h 30kW 36 91cm for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C C...

Страница 16: ...om the finished outside wall to the center of the pipe on the fireplace Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe Outside Corner Inside Corner G Combustible 6...

Страница 17: ...rst frame in opening Combustible Interior Walls Cut a 121 2 H x 101 2 W 318 x 267 mm hole through the interior wall Combustible Exterior Walls Cut a 101 2 H x 101 2 W 267 x 267 mm square hole through...

Страница 18: ...rials is 3 on top and 1 from bottom and sides unless otherwise noted Exception Outside wall with firestop 1 all around pipes are allowed If the vertical run is 71 2 feet or more off the top of the fir...

Страница 19: ...ow is used in the horizontal vent run level height maintained the horizontal vent length is reduced by 36 914 mm Figure 22 This does not apply if the 90 elbows are used to increase or redirect a verti...

Страница 20: ...vent pipe end Allow 1 4 minimum rise per foot Figure 25 1 Locate and cut the vent opening in the wall For com bustible walls first frame in opening Combustible Interior Walls Cut a 111 2 H x 91 2 W 2...

Страница 21: ...imately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel Figure 27 3 Install vent...

Страница 22: ...izontal run For each 45 elbow used on the horizontal plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1x45 elbows 8 5 2 6 m 2x45 elbo...

Страница 23: ...31 Maximum Elbow Usage FP1969 offset w wallstrap Figure 32 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firstop FP1669 FLAT CEILING INSTALLATION 1 Cut a 101 2 267 mm...

Страница 24: ...joining roof lines steep pitched roofs and other similar factors may cause poor draft or down drafting in high winds Increasing the vent height may solve this problem NOTE If the vent pipe passes thro...

Страница 25: ...ance between inside and outside pipe The inner and outer adapter rings are required to start all flex runs Never install damaged or torn flexible venting Over tightening clamps may rip tear or otherwi...

Страница 26: ...five feet intervals Metal strapping properly secured is an acceptable means to support the flexible vent 5 Flexible vent spacers are to be installed at inter vals prescribed by the flexible vent manuf...

Страница 27: ...ust above gear clamp 4 x 7 Rigid Pipe Length Flex to Pipe Adapter DVFFA 8 Gear Clamp 13 4 Flexible Pipe and Adapter Outer Collar Overlap UL1777 Flex Vent Figure 43 Typical Pipe Connection Gear Clamp F...

Страница 28: ...o test gauge connection Purchase the CSA design certified equip ment shutoff valve from your dealer For propane LP connections only the installer must supply an external regulator The external regulat...

Страница 29: ...em valves CAUTION A manual shutoff valve must be installed upstream of the appliance Union tee and plugged 1 8 NPT pressure tapping point should be installed upstream of the appliance Figure 46 CAUTIO...

Страница 30: ...Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are used for back up during power outages 2 The Sign...

Страница 31: ...imum by using two 2 SCSWEK cables plugged together Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from the com mand center Attach the connector to th...

Страница 32: ...LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in...

Страница 33: ...not work correctly SIGNATURE COMMAND BLOWER BLOTSDVSC The BLOTSDVSC Blower Kit requires the SCSACM A C Module and the TSFSC remote to install and operate this kit Refer to blower instructions for ins...

Страница 34: ...g eyebrow 1 Unhook top louver assembly Set aside Figure 53 2 Attach canopy to underside of top outer shell with three 3 screws provided Figure 54 3 Hook top louver assembly back into place FP2417 louv...

Страница 35: ...500DVM 1 Piece 1 Install floor brick before installing logs or rock wool 2 Install the rear brick panel by sliding it over the existing bracket fastened to the rear of the firebox 3 Remove the existi...

Страница 36: ...the bracket Fig ure 58 LG665 Rear Log LG667 DVM left middle log Figure 57 Place Rear Log Left Middle Log LG667 3 Place the left middle log by aligning the holes in the bottom of the log with the two p...

Страница 37: ...setting the notch on the bottom of the log on the very far right tong of the grate and resting the log on the leg of the grate Figure 60 LG670 DVM upper logs Upper Left Log Upper Middle Log Upper Righ...

Страница 38: ...s Laissez refroidir le panneau vitr avant d y toucher Ne laisser jamais les enfants toucher le panneau vitr A barrier designed to reduce the risk of burns from the hot viewing glass is provided with t...

Страница 39: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch wil...

Страница 40: ...s the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will light 6 Once pilot flame is...

Страница 41: ...tion for Transmitter X X X X X Child Proof Lock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode Thermos...

Страница 42: ...stand ing pilot and intermittent pilot 2 After the above operation one beep for standing pi lot or two beeps for intermittent pilot will be given as confirmation Six hour Safety Shutdown Option Defaul...

Страница 43: ...the OFF t button 3 times OR for Memory Off hold the OFF t button 3 seconds or turn off wall switch Flame Height Up Press the ON s button once to turn on the fireplace with maximum flame height Flame...

Страница 44: ...emove any lint or foreign material with a brush or vacuum BURNER FLAME The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation...

Страница 45: ...ed Handle glass door with care to avoid striking or scratch ing it on hard objects To clean glass door follow Glass Removal procedure outlined in the Canopy Installation and Glass Removal section Film...

Страница 46: ...per foot Do not run the pipe level or downward C Improper vent cap installation C Check for proper installation and freedom from debris or blockage 3 Glass Soots A Flame impingement on logs A Install...

Страница 47: ...und Check gas supply Go through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery vol...

Страница 48: ...48 20306747 DVM Series Direct Vent Gas Fireplace REPLACEMENT PARTS FIREBOX COMPONENTS 1 5 3 2 4 7 10 6 9 8 8 752525 DVM firebox parts 11...

Страница 49: ...K 56D2269K 5 Eyebrow 1 56D4041 56D4038 6 Insulation Board 1 56D2197 56D2216K 11 Safety Screen Barrier 1 20306643K 20306649K Accessories Field Installed Options 7 Firebrick Tavern Brown 1 FBMDV500TB FB...

Страница 50: ...50 20306747 DVM Series Direct Vent Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 1 2 3 4 19 5 6 7 8 9 13 14 15 16 17 752523 MDV DVM SC parts 12...

Страница 51: ...not shown 1 80D0010 80D0010 80D0010 80D0010 11 Wire Command Ctr Control Box 2 not shown 1 80D0008 80D0008 80D0008 80D0008 12 A C Adapter 6 Volt 1 80D0041 80D0041 80D0041 80D0041 Accessories 13 Hand He...

Страница 52: ...1 Rear Log 1 1 75D2016 75D2016 2 Left Middle Log 2 1 75D2017 75D2017 3 Right Middle Log 3 1 75D2018 75D2018 4 Left Front Log 4 1 75D2019 75D2019 5 Right Front Log 5 1 75D2020 75D2020 6 Upper Left Log...

Страница 53: ...48PWM 3 Mesh Glass Cover not shown 1 MDV500SDC MDV600SDC 4 Cabinet Door Frame Black 1 VSDVC500CDFB VSDVC600CDFB 4 Cabinet Door Frame Iron Age 1 VSDVC500CDFIA VSDVC600CDFIA 4 Cabinet Door w Screen Blac...

Страница 54: ...Cap 46DVS HRCS 1 1 Sconce Termination Cap aluminum 46DVA HSC 2 1 Low Profile Vertical Termination Cap 46DVA VC 980 4DT VC 4DVT 3 6 6 Pipe Length galvanized 46DVA 06 908 4DT 06 4DV6 3 6 9 Pipe Length g...

Страница 55: ...48 Adapter BHSF58TK 1 8 Horizontal Termination w 1 Firestop BHR58T 8 1 1 Horizontal High Wind Termination Cap 58DVA HC 1285 5DT HC 1 1 Horizontal Temination Cap 5DHT 2 1 Vertical Termination 58DVA VC...

Страница 56: ...TDVPA 4 12 18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Ve...

Страница 57: ...36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 5 x 8 to 4 x 7 Adapter 7TDVP58 Flex Adapter Starter Kit DVFFA 8 Twist Lock Elbows 45 Elbow for...

Страница 58: ...have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be install...

Страница 59: ...be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect...

Страница 60: ...ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS FIREPLACE...

Отзывы: