DVM Series Direct Vent Gas Fireplace
VENTING INSTALLATION
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
2 4 6 8 10 12 14 16 18 20
eg: A
FP2132
sidewall vent graph
HOW TO USE THE VENT GRAPH
The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimensions
of the vent system.
1. Determine the height of the center of the horizontal vent
pipe exiting through the outer wall. Using this dimension
on the Sidewall Vent Graph below, locate the point
intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the fire
-
place in accordance with same.
Example: If the vertical dimension from the floor of the
fireplace is 11' (3.4 m) the horizontal run to the face of
the outer wall must not exceed 16' (4.9 m).
Sidewall Vent Graph showing the relationship between
vertical and horizontal dimensions for a Direct Vent flue
system.
Dimensions in Feet
Figure 10 -
Rear Wall Venting Graph
(No Horizontal Elbows)
Horizontal dimension from the
finished outside wall to the center
of the pipe on the fireplace
Vertical Dimension From the Floor of Unit to the
Center
of
the
Horizontal
V
ent
Pipe
Outside Corner
Inside Corner
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
G
Balcony -
with no side wall
M =
Combustible &
Noncombustible
12" (305 mm)
M
Balcony -
with perpendicular side wall
M =
12" (305 mm)
P =
6” (152 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
E
= Min. 2” (51 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O
= 8’ (2.4 m) Min.
O
P
V
V
V
584-15
D
Min.
= Number of Termination caps x 3
C
Max.
= (2 / Number termination caps) x D
Actual
*NOTE:
Termination in an alcove space (spaces open only on one side
and with an overhang) is permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 1. There must be a 3' (914 mm) min
-
imum between termination caps. 2. All mechanical air intakes within 10'
(1 m) of a termination cap must be a minimum of 3' (914 mm) below the
termination cap. 3. All gravity air intakes within 3' (914 mm) of a termina-
tion cap must be a minimum of 1' (305 mm) below the termination cap.
TERMINATION CLEARANCES
Termination clearances for buildings with combustible and non-combustible exteriors.
No. of
Caps
D
min
.
C
max
.
1
3' (914 mm) 2 x
D
actual
2
6' (1.8 m) 1 x
D
actual
3
9' (2.7 m) 2/3 x
D
actual
4
12' (3.7 m) 1/2 x
D
actual