9
20306747
DVM Series Direct Vent Gas Fireplace
PRE-INSTALLATION INFORMATION
CLEARANCES TO COMBUSTIBLES
72”
(1829 mm)
Minimum
12”
(305 mm)
Minimum
6”
(152 mm)
Min.
FP2408
DVM MDV clearances
12”
(305 mm)
Maximum Depth
Ceiling
Side Wall
Combustible
Mantel
FP2408
Figure 4 -
Ceiling and Side Wall Clearances
12”
10”
8”
6”
4”
2
¹⁄₂
”
12"
10
³⁄₄
”
9
¹⁄₂
”
8
¹⁄₄
”
7”
6”
FP2409
Mantel clearance
Top of Fireplace
Opening
Stud
Header
Standoff
Insulation
Board
FP2409
Side View
45°
1”
2
¹⁄₂
”
3”
5”
6”
1¹⁄₂
”
3¹⁄₂
”
4¹⁄₂
”
FP2410
mantel leg clearance
Finish Wall
Combustible
Material Area
FP2410
Figure 5 -
Mantel Clearances
MANTEL CLEARANCES
NOTE:
The combustible area above the facing must not protrude
more than 1/2" from the facing. If it does, it is considered a mantel
and must meet the mantel requirements listed in this manual.
Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire
hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on
carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending
full width and depth of the appliance.
WARNING
Never obstruct or modify the air inlet or outlet grilles
(louvers). This may create a fire hazard.
WARNING