background image

CFDV Series Gas Fireplace

58

20306739

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fi tter 
when installed within the Commonwealth of Massachusetts.

Any residence with a direct vent product must have a carbon 
monoxide (CO) detector installed in the residence.

Installation of the fi replace or vented gas log in the State of 
Massachusetts requires the damper to be permanently removed 
or welded in the fully open position.

In addition, a naturally vented gas log may not be installed in a 
bedroom or bathroom in the State of Massachusetts.

Flex line installation must not exceed 36 inches and must have a 
T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fi tter 
when installed within the Commonwealth of Massachusetts.

In addition, vent free products may not be installed in a 
bedroom or bathroom regardless of size or type in the State of 
Massachusetts.

Flex line installation must not exceed 36 inches and must have a 
T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise 10.8.3 by adding the following additional 
requirements:

(a)  For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in whole 
or in part for residential purposes, including those owned 
or operated by the Commonwealth and where the side wall 
exhaust vent termination is less than seven (7) feet above 
fi nished grade in the area of the venting, including but not limited 
to decks and porches, the following requirements shall be 
satisfi ed:

1. 

Installation of carbon monoxide detectors. 

At the time 

of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gas fi tter shall observe 
that a hard wired carbon monoxide detector with an alarm and 
battery back-up is installed on the fl oor level where the gas 
equipment is to be installed. In addition, the installing plumber 
or gas fi tter shall observe that a battery operated or hard wired 
carbon monoxide detector with an alarm is installed on each 
additional level of the dwelling, building or structure served by 
the side wall horizontal vented gas fueled equipment. It shall be 
the responsibility of the property owner to secure the services of 
qualifi ed licensed professionals for the installation of hard wired 
carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 
hard wired carbon monoxide detector with alarm and battery 
back-up may be installed on the next adjacent fl oor level.

 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply with the 
above requirements; provided, however, that during said thirty 
(30) day period, a battery operated carbon monoxide detector 
with an alarm shall be installed.

MASSACHUSETTS RESIDENTS ONLY

2. 

Approved Carbon Monoxide Detectors. 

Each carbon 

monoxide detector as required in accordance with the above 
provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certifi ed.

3. 

Signage.

 A metal or plastic identifi cation plate shall 

be permanently mounted to the exterior of the building at a 
minimum height of eight (8) feet above grade directly in line with 
the exhaust vent terminal for the horizontally vented gas fueled 
heating appliance or equipment. The sign shall read, in print size 
no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4. 

Inspection.

 The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment shall not approve 
the installation unless, upon inspection, the inspector observes 
carbon monoxide detectors and signage installed in accordance 
with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 
as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 
dwelling, building or structure used in whole or in part for 
residential purposes.

(c)  

Manufacturer requirements — Gas Equipment Venting 

System Provided. 

When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides 
a venting system design or venting system components with 
the equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system shall 
include:

1. Detailed instructions for the installation of the venting 

system design or the venting system components; and

2. A complete parts list for the venting system design or 

venting system.

(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled equipment 
does not provide the parts for venting the fl ue gases, but 
identifi es “special venting systems,” the following requirements 
shall be satisfi ed by the manufacturer:

1. The referenced "special venting system" instructions 

shall be included with the appliance or equipment installation 
instructions; and

2. The “special venting systems” shall be Product Approved 

by the Board, and the instructions for that system shall include a 
parts list and detailed installation instructions.

(e)  A copy of all installation instructions for all Product Approved 
side wall horizontally vented gas fueled equipment, all venting 
instructions, all parts lists for venting instructions, and/or all 
venting design

Please read and follow these special requirements

Содержание 33CFDV(N/P)(V/I)SB

Страница 1: ...Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer servi...

Страница 2: ...BLOT 31 Optional Fan Blower System FK12 31 Operating Instructions Millivolt 32 For Your Safety Read Before Lighting 32 What To Do If You Smell Gas 32 Lighting Pilot for the First Time 32 Lighting Pilo...

Страница 3: ...all service or repair the fireplace Have burner system inspected annually by a qualified service person IMPORTANT SAFETY INFORMATION This fireplace is a vented product This fireplace must be properly...

Страница 4: ...t or any other accessory not approved for use with this fireplace 24 Do not operate appliance with the glass front removed cracked or broken Replacement of the glass should be done by a licensed quali...

Страница 5: ...S Natural Gas Propane LP Inlet Minimum 5 5 w c 11 0 w c Inlet Maximum 14 0 w c 14 0 w c Manifold Pressure 3 5 w c 10 0 w c Off Pilot On Knob Hi Lo Knob FP3011 FIREPLACE CONTROLS COLD CLIMATE OPTION IP...

Страница 6: ...ents and for firebox dimensions The framing headers may rest on the top of the firebox standoffs Do not bring headers below top of standoffs The firebox may be installed directly on a combustible floo...

Страница 7: ...343 4 883 mm D 27 689 mm 291 8 740 mm 331 8 841 mm E 18 457 mm 197 8 505 mm 197 8 505 mm F 157 8 430 mm 157 8 430 mm 157 8 430 mm G 211 8 537 mm 221 8 562 mm 261 2 673 mm H 231 4 591 mm 255 8 657 mm...

Страница 8: ...al codes includ ing permits and inspections The following factors should be taken into consideration Clearance to side wall ceiling woodwork and windows Minimum clearances to combustibles must be main...

Страница 9: ...ure fireplace to the floor Use four 4 screws to attach fireplace to framing The side nailing flanges are 1 2 or 5 8 to accommodate different wall thickness FINISHING MATERIAL NOTE Any wiring i e remot...

Страница 10: ...aside Figure 9 Remove Screws Remove Screws 7 Collar FP3022 Figure 9 Remove 7 Collar and Gasket 3 Remove the plate with the 4 collar and gasket by re moving four 4 screws Set aside Figure 10 4 Remove...

Страница 11: ...Gasket 7 Remove the small square plate and gasket by removing four 4 screws Set aside Figure 13 Remove Screws Small Square Plate FP3027 Figure 13 Remove Small Square Plate and Gasket 8 Install the pl...

Страница 12: ...h the side wall or vertical through the roof Only Vermont Castings Group venting components specifically approved and labeled for this fireplace may be used Flexible UL1777 listed venting may be used...

Страница 13: ...ances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanently closed...

Страница 14: ...ocal codes and or the current National Fuel Code ANSI Z223 1 NFPA 54 Canadian Installations The venting system must be installed in accordance with the current CSA B149 1 installation code FLEX VENT P...

Страница 15: ...assembly the joints we suggest put ting a lubricant Vaseline or similar on the male end of the twist lock pipe prior to assembly Male End Female End Screw Holes TWL100 Figure 18 Twist lock Pipe Joints...

Страница 16: ...and position the fire place in accordance with same EXAMPLE A If the vertical dimension from the floor of the unit is 11 3 4 m the horizontal run to the face of the outer wall must not exceed 14 4 3...

Страница 17: ...ARNING Rear Top Vent Vertical Side wall Horizontal sections of this vent system require a minimum of 3 76 mm clearances to combustibles at the top of the flue and 1 25 mm clearance at the sides and bo...

Страница 18: ...ombustible Walls Hole opening should be 71 2 191 mm diameter Step 2 Secure firestop to the inside frame center in the 95 8 x 95 8 vent opening Step 3 Measure the horizontal length requirement for the...

Страница 19: ...bus tible materials is 3 76 mm on top and 1 25 mm on the bottom and sides unless otherwise noted When vent termination exits through foundations less than 20 508 mm below siding outcrop the vent pipe...

Страница 20: ...run the length of the horizontal run MUST be reduced by 18 457 mm This does not apply if the 45 elbows are installed on the vertical part of the vent system The maximum number of elbow degrees in a sy...

Страница 21: ...ed flue restrictors onto the top edge of the firebox flue adapter according to the Vertical Side wall Installation Flue Restrictor Chart Step 1 Locate vent opening on the wall It may be necessary to f...

Страница 22: ...w Step 1 and 2 on Page 21 Step 3 Install the four 4 spacer springs on the 4 flex vent pipe When installing the spacer springs around the 4 pipe stretch the spring to approximately 15 381 mm wrap the s...

Страница 23: ...nting clearances are observed If venting system is installed below ground we rec ommend a window well with adequate and proper drainage to be installed around the termination area If installing a snor...

Страница 24: ...uced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1 x 45 elbow 8 5 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 5 m vertical rise is required Two sets of 45 elbow offsets may be...

Страница 25: ...ual to 93 4 x 93 4 248 x 248 mm 4 Proceed to plumb for additional openings through the roof In all cases the opening must provide a minimum of 1 inch clearance to the vent pipe i e the hole must be at...

Страница 26: ...feet Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 H Minimum height from roof to lowest d...

Страница 27: ...o between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regula tor damage could occur Install external regulator with the vent pointing down as shown in Figure 51...

Страница 28: ...t lightly to male threads This will prevent excess sealant from going into pipe Excess seal ant in pipe could result in clogged burner system valve We recommend that you install a sediment trap drip l...

Страница 29: ...he factory 3 The junction box cover has a factory installed romex style strain relief connector After connecting the wires route the wire leads through this connector Refer to the wiring diagram in Fi...

Страница 30: ...m for Wall Switch ELECTRICAL INSTALLATION MILLIVOLT REMOTE WALL SWITCH Position the wall switch Do not extend beyond the 15 feet of wire OPTIONAL DC REMOTE SYSTEMS See section entitled Hearth Mount in...

Страница 31: ...ed This system requires that 110 120 VAC to be wired to the factory installed junction box before the fireplace is permanently installed Figure 56 Black Black Green Black Black White Thermostatic Swit...

Страница 32: ...ified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician...

Страница 33: ...1 and 2 LIGHTING PILOT Pilot Position Check for gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff...

Страница 34: ...position It will take less than four 4 seconds for the burner to ignite MAIN BURNER SWITCH This switch allows you to turn on and to turn off the main burner without using the gas valve knob is in the...

Страница 35: ...ot use open flame to check for gas leaks ELECTRICAL WIRING General 1 This fireplace is equipped with an IPI control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junct...

Страница 36: ...leads through this connector Refer to the wiring diagram in Figure 59 Figure 59 Junction Box Wiring Diagram Junction Box Factory Supplied Not Supplied 120V AC 60Hz ELECTRICAL INSTALLATION IPI WALL SW...

Страница 37: ...Switch DC Power Green Ground Gas In Gas Out Pilot Gas Tubing Valve Cold Climate Switch Main Switch ELECTRICAL INSTALLATION IPI CAUTION Electrical connections should only be performedbyaqualified lice...

Страница 38: ...one Follow the gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Turn Master Switch to ON position by hand Never use tools If the switch will not function b...

Страница 39: ...ow B in the safety information on Page 38 If you do not smell gas go to next step 4 Press the wall switch to the ON position Sparker will spark and pilot flame will light 5 Once pilot flame is establi...

Страница 40: ...il Two RED 1 time No Sensor Signal Three RED 1 time Trial Lockout One GREEN every 2 seconds until manual reset Flames Loss Lockout One RED GREEN every 2 seconds until manual reset AC Power On GREEN So...

Страница 41: ...elease the two 2 latches on the top of the fireplace by pulling forward and up Figure 61 3 Tilt glass frame out and lift glass frame up and away Figure 62 4 Set glass frame aside Figure 62 Remove Safe...

Страница 42: ...is blue and only in the center turn off unit and let cool After unit is cool remove logs and check to make sure rock wool is placed correctly Replace logs NOTE The type of installation vent system con...

Страница 43: ...eld 3 Install the center firebrick panel on the back wall first Stand firebrick panel straight up against the back of fireplace with the bottom edge at bottom of inner firebox 4 Repeat Step 3 with the...

Страница 44: ...tab in the center front of the false hearth up to a 90 angle Figure 71 Place the top log 4 by resting the square notch located on the bottom of the log over the tab mentioned above Rest the top part...

Страница 45: ...Center Tab Figure 71 LG1183 Figure 73 WARNING Do not sprinkle the lava rock on top of the burner This may cause potential sooting glass breakage and a fire hazard LAVA ROCK PLACEMENT Sprinkle lava ro...

Страница 46: ...g the latches on top of the fireplaces and tilting frame for ward Lift off and set aside 4 Remove the logs if they are installed Vacuum the rock wool off the burner 5 Remove the four 4 pin log plate a...

Страница 47: ...duals If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance Any safety screen guard or barrier removed for servicing the appliance must be rep...

Страница 48: ...eplace manufacturer No substitute materials may be used Handle glass door with care to avoid striking or scratch ing it on hard objects To clean glass door follow Glass Removal procedure outlined in t...

Страница 49: ...re that the thermocouple connection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other m...

Страница 50: ...ss does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check valve connections Check power supply go through A...

Страница 51: ...Glass Kit Diamond GKD Glass Kit Onyx GKO Glass Kit Sapphire GKS Blower Kits T Stat Blower w Speed Control BLOT Manual Blower FK12 Speed Control 26D0746 SYMPTOM POSSIBLE CAUSE ACTION The pilot and mai...

Страница 52: ...6161K 20306695K 20306701K Kits Sold Separately 3 Blower 1 BLOT BLOT BLOT 4 Firebrick Kit Cottage Clay 1 FB33CFDVCC FB36CFDVCC FB42CFDVCC 4 Firebrick Kit Cottage Red 1 FB33CFDVCR FB36CFDVCR FB42CFDVCR...

Страница 53: ...Pilot Assembly 1 37D0018K 37D0019K 37D0018K 37D0019K 37D0018K 37D0019K 5 Replacement Thermocouple 1 24D0808 24D0808 24D0808 24D0808 24D0808 24D0808 6 Replacement Igniter and Wire 1 10001297 10001297 1...

Страница 54: ...E0101 95E0101 95E0101 4 Pilot Assembly 1 95E0103 95D0104 95E0103 95E0104 95E0103 95E0104 5 Control Board 1 95E0108 95E0108 95E0108 95E0108 95E0108 95E0108 6 Injector 1 58D0061 62D3005 59D0062 20H3146...

Страница 55: ...ck Pipe 20 Rigid Pipe single pack 7TDVP20 30 Flex Pipe single pack 7FDVP30 12 18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack...

Страница 56: ...ination Screen Guard 7TBSG Up and Out Starter Kit w 40 Flex Pipe Firestop Cool 7FDVSCTK Touch Termination w Siding Shield and 2 ea Clamp Bands Twist Lock Pipe 20 Termination Pipe 8 pack 7TDVP20 8 10 1...

Страница 57: ...pipe length galvanized 46DVA 12 3 6 24 pipe length galvanized 46DVA 24 3 6 36 pipe length galvanized 46DVA 36 3 6 48 pipe length galvanized 46DVA 48 4 6 81 2 pipe length galvanized 46DVA 08A 4 6 16 p...

Страница 58: ...o comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS RESIDENTS ONLY 2...

Страница 59: ...Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage...

Страница 60: ...EL ENERGUIDE RATINGS FIREPLACE EFFICIENCY PERCENTAGE D O E AFUE PERCENTAGE 33CFDVNV 58 3 59 70 33CFDVPV 67 1 63 83 33CFDVNI 61 9 59 70 33CFDVPI 72 6 63 83 36CFDVNV 63 0 62 01 36CFDVPV 67 7 66 16 36CFD...

Отзывы: