Installation Guide

Power Monitoring

E30E Series

TM

The E30E consists of a BACnet virtual router and one or two 42-channel branch circuit meters. The BACnet virtual router has its 
own device object and an internal BACnet network. The branch circuit monitors have their own device objects that are logical 
devices on the network internal to (beneath) the virtual router. It is critical that the network number of the virtual router’s 
internal network be different than any other network number in your entire BACnet system. The network number is set to 50 at 
the factory, but can be changed in the GUI or by writing to the Present_Value of the AV2 data object associated with that device. 
Changes to the network number do not take affect until the E30E is re-started, either from the GUI or by cycling the power.

The default Device ID of the virtual router is the Device_Offset parameter, which is set to 5000 at the factory, but can be changed 
in the GUI or by writing to Present_Value of the the AV1 data object associated with that device. Changes to the network number 
do not take affect until the E30E is re-started, either from the GUI or by cycling the power. The default Device IDs are numbered 
to consecutively follow the Device ID of the virtual router (e.g. if the Device_Offset parameter is 50000, the virtual router has a 
Device_ID of 50000, the branch circuit monitor called Panel 1 has a Device_ID of 50001 and  the branch circuit monitor called 
Panel 2 (if present) has a Device_ID of 50002.

All Device_IDs are writable. Once a device’s Object_Identifier is overwritten, changes to the ID Offset no longer affect that 
Object_Identifier, even in Discovery mode. Make further changes to the value by writing the Object_Identifier property.

The default Object_Name property value of each device object is an abbreviated name of the meter series discovered with 
an underscore and the Modbus address of the meter appended to it. The Object_Name is a writable property. Once a device’s 
Object_Name is overwritten, the Object_Name does not revert to the initial default, even in Discovery mode. Make further 
changes to the value by writing the Object_name property.

The E30E supports Subscribe_COV, with default COV increment values assigned as shown in the data object tables. If these values 
are not appropriate for a specific application, write them as needed when they are subscribed. On subsequent power cycles, no 
subscriptions are active and the COV increments return to their default values.

With few exceptions, any data values written to AV objects are accepted (without error) by the data object and passed through 
to the corresponding Modbus register. There is no direct indication via the BACnet protocol if invalid values are rejected. After an 
invalid value is written to the Present_Value of an AV, subsequent reads of that property return the new (invalid) value until the 
next time the E30E refreshes its data (this may take several seconds). 

BBMD Support

When the E30E is in BACnet IP mode, it can be configured as a BBMD device by entering “BBMD” in the Enable BBMD Support field 
in the GUI, adding devices to a comma separated value text file named bdt.ini, and loading it onto the device. The example below 
shows the syntax required for the bdt.ini file. All lines beginning with two forward slashes are interpreted as comments. Use 
exactly one line per device added, separated by commas (no spaces). The file must include an entry (line) for each BBMD device 
in the BAcnet enterprise, including the E30E itself. Note:  the default gateway address in the network setup must be correct for 
BBMD support to operate correctly. Once edited, upload the btd.ini file to the gateway through the GUI. Click the <Diagnostics and 
Debugging> button in the lower right corner of the GUI and follow the folder tree under Navigation to the following folder: “Veris 
Industries E3x Series Gateway/Setup/File Transfer.” Select the “General” tab (this is important - using the wrong tab can overwrite 
critical files). Click the <Browse> button and select your bdt.ini file. Then click <Submit>. The GUI quickly indicates “The file 
was updated successfully.” Click the <System Restart> button, click <OK> on the confirmation dialog and wait for the gateway 
to reinitialize (takes about 30 seconds). BBMD changes are made by uploading a new btd.ini file. After setting the GUI to enable 
BBMD support and transferring a new or revised bdt.ini file, restart the E30E to load the file. BBMD support can be disabled in the 
GUI by entering “-” (a hyphen) in the Enable BBMD Supprt filed in the GUI.

// Bdt.ini
// The format of this table must be (without the forward slashes - they are comment indicators):
//
//BBMD IP_Address , BBMD port , BBMD subnet Mask
//
147.26.116.217,47808,255.255.255.255
172.16.17.198,47808,255.255.255.255

General BACnet 
Programming 
Information

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание E30A042

Страница 1: ...d avoid the hazards involved NEC2011 Article 100 No responsibility is assumed byVeris Industries for any consequences arising out of the use of this material DANGER Product Identification Product Over...

Страница 2: ...ency 2560 Hz Update Rate Modbus 1 8 seconds both panels BACnet 14 seconds SNMP 20 seconds ETHERNET COMMUNICATION Physical Interface RJ45 connector with 10 100 Mbit Ethernet Protocols Supported Modbus...

Страница 3: ...enter 16 4 417 mm 1 7 43 mm 0 4 10 mm opening 0 7 18 mm on center 2 0 50 mm 1 3 32 mm 15 7 399 mm 0 4 10 mm opening 0 7 18 mm on center 1 3 32 mm 12 3 312 mm 0 4 10 mm opening 0 7 18 mm on center 0 9...

Страница 4: ...g and power calculations 6 Control Mains Power Connection Easy 2 wire 100 277 VAC 50 60 Hz connection 7 Auxiliary Inputs These 0 333 VAC inputs are used for monitoring the main breaker or other high a...

Страница 5: ...3 6 1 4 1 40845 1 30 1 1 6 3 4 0 For models with 42 channels or more these features are configured independently for each panel Logical Circuit support The E30E can be configured to map any set of 1...

Страница 6: ...r phase Voltage L L multi phase average and per phase Voltage L N multi phase average and per phase Frequency phase A Demand Measurements Current present demand multi phase average and per phase Real...

Страница 7: ...circuit numbers in the field during commissioning by writing to Modbus Register 6 or use the free configuration software at www veris com The examples in this graphic show the 21 current sensor strips...

Страница 8: ...grounding connection is located on the housing see below Use this stud to ground the device when it is mounted on a nonconductive surface CURRENT SENSOR STRIP CURRENT SENSOR STRIP CURRENT SENSOR STRI...

Страница 9: ...the E3x Configuration Tool to view the phase angles of active circuits to help verify that those circuits are connected to and mapped to the proper voltage phases See the E3x Commissioning Guide www...

Страница 10: ...nd termination the value and placement of these resistors varies for each standard The E30E does not implement any RS 485 line polarization bias or termination internally For the RS 485 cable use shie...

Страница 11: ...ed to work on the network and is being accessed from a PC on that same network open a web browser and enter the IP address of the E30E into the address URL field on the browser Press enter The GUI lau...

Страница 12: ...et to its factory default IP address of 192 168 1 24 set the PC to an unused static IP address on the 192 168 1 xxx subnet where xxx is any value between 1 and 255 except 24 Set the subnet mask to 255...

Страница 13: ...se the following IP Address Make note of the IP address that appears then enter the static IP address e g if the E30E Series is still set to its default address of 192 168 1 24 then change it to 192 1...

Страница 14: ...s Installation Guide Power Monitoring E30E Series TM UsingtheGUItosetuptheIPaddressforuseonyournetwork 1 Access the GUI according the instructions in the Accessing the Graphical User Interface GUI sec...

Страница 15: ...IP Address Settings menu b Enter the desired IP address in the N1_IP_Address field in the format xxx xxx xxx xxx c If necessary change the Subnet Mask by entering the appropriate new value in the N1_N...

Страница 16: ...iscovery mode default deletes profiles and rediscovers them when the device is powered again The results are the same unless the profile configuration is intentionally altered Profile selection and di...

Страница 17: ...MS TP trunk and any devices beyond it This virtual router creates an exclusive BACnet network on which the meter s BACnet devices reside This network must have a BACnet network number that is differen...

Страница 18: ...eters described above for BACnet MS TP mode One additional parameter BACnet_IP_Port is used to set the UDP port Most BACnet systems use the default port 47808 decimal 0xBAC0 hex that is recommended in...

Страница 19: ...two unique parameters The SNMP_Community string is used to control access to the device Whatever value entered must be used in the MIB browser or SNMP access software to communicate with this device...

Страница 20: ...on settings using the GUI Valid network numbers range from 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID n...

Страница 21: ...WP B K 1 10 BIBB Data Sharing WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2 5 BIBB Alarm and Event ACK B AE...

Страница 22: ...property The E30E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specific application write them as nee...

Страница 23: ...ected to the Panel 1A and Panel 1B connectors and to the data set under Modbus address 1 or BACnet device identified as Node_1 in the GUI Panel 2 corresponds to the branch current sensor strips connec...

Страница 24: ...ctual strip installation Verify phase rotation of breakers firmware rev 1 012 or higher allows for custom rotation if needed Current reading is not as expected or reading is on different CT number tha...

Отзывы: