6. Connect 0.333 VAC current transformers (CTs) to the conductors to be monitored by snapping the CTs around the lines,
observing local codes regarding bending radius.
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Panel 2
Panel 1
Note: The E30E measures and reports the phase angle of each voltage input and each CT (when there is active current
through the primary of that CT). Use the E3x Configuration Tool to view the phase angles of active circuits to help verify
that those circuits are connected to and mapped to the proper voltage phases. See the E3x Commissioning Guide (www.
veris.com) for instructions on how to download and operate the tool from a PC.
For all steps in this section, when tightening terminals, apply the correct torque.
Aux Inputs: 3.5 to 4.4 in-lb (0.4 to 0.5 N-m); all other terminals: 4.4 to 5.3 in-lb (0.5 to 0.6 N-m).
1. Wire the Aux input CTs to the E30E. Note: For Veris CTs, X1 is the white lead, X2 is the black lead.
1
2
3 N
X1
X1
X1
X1
X2
X2
X2
X2
N 3
2
1
X1
X1
X1
X1
X2
X2
X2
X2
2. Connect 2-wire 100-277 VAC power to the control power terminals. Observe polarity. Connect voltage lines to the voltage taps.
Equip voltage lines with fuses and disconnects as required.
Voltage taps are shared by both panels.
L-L
V1
V2/N
L-N
Voltage Inputs
90-300V 50/60Hz
VN V3 V2
V1
Control Power
100-277V 50/60Hz 15VA
V V2/N