Installation Guide
Power Monitoring
E30E Series
TM
3. Verify that the serial numbers printed on the current sensor strips and on the E30E match. The board and the strips are sold as a
calibrated set.
4. Install the E30E in the panel (hardware not provided). A grounding connection is located on the housing (see below). Use this
stud to ground the device when it is mounted on a nonconductive surface.
CURRENT SENSOR STRIP
CURRENT SENSOR STRIP
CURRENT SENSOR STRIP
CURRENT SENSOR STRIP
Panel 2
Panel 1
E30E
Ground
5. Connect the current sensor ribbon cables to the 50-pin connectors on the E30E. The label on the strip indicates which connector
to use on the E30E (e.g. connect the strip labeled “Panel 1A” to the bottom right connector on the board). Orient the cables so
that the plastic key on the E30E connector aligns with the keyhole cutout on the ribbon cable connector, as shown below.
Panel 1,
Strip A
Panel 1,
Strip B
Panel 2,
Strip A
Panel 2,
Strip B
Align ribbon
cable key with
connector keyhole.
Installation (cont.)