IG-305-EN version 01; 07/04/2020
11
General Instructions
Outdoor cubicles:
cgmcosmos
,
cgm
.3 and
cgm
.800 systems
Storage
3. Storage
If it needs to be stored, the equipment must be placed on
dry ground or on top of damp-proof insulating material, still
in its original packaging.
After prolonged storage, clean all the insulating parts
carefully before commissioning the equipment. The
enclosure must be cleaned with a clean, dry lint-free cloth.
Storing INDOORS in the following conditions is reco-
mmended:
1.
Ambient air temperature must not exceed 40 ºC and
its average value, measured over a period of 24 hours,
must not exceed 35 ºC.
2.
The ambient air temperature must not drop below
- 5 °C. There are also cubicles with storage temperature
up to - 40 °C.
3.
The switchgear must be protected from direct solar
radiation.
4.
Altitude, both in transport and in storage, must not
exceed 2000 m.
5.
The ambient air must not have any signifi cant
contamination from dust, smoke, corrosive and/or
infl ammable gases, vapours or salt.
6.
The switchgear must be protected from the rain, and
the humidity conditions must be as follows:
a.
the average relative humidity value, measured over
a period of 24 hours, must not exceed 95 %.
b.
the average water vapour pressure value, measured
over a period of 24 hours, must not exceed 2.2 kPa.
c.
the average relative humidity value, measured over
a period of one month, must not exceed 90 %.
d.
the average water vapour pressure value, measured
over a period of one month, must not exceed
1.8 kPa.
7.
During transport, vibrations caused by external factors
or seismic movements must be insignifi cant.
Any other conditions must be notifi ed beforehand,
since the equipment must be factory-adjusted to
atmospheric pressure at the destination.
If this is not the case, the manometer needle may
indicate an incorrect value, even if the equipment's
internal pressure is correct.