Recommended sequence of operations
General Instructions
Outdoor cubicles:
cgmcosmos
,
cgm
.3 and
cgm
.800 systems
3.
From inside the cable compartment, unscrew the
12 DIN933M8 hex bolts (6 on each side) that secure the
cubicles to the external enclosure.
Tool:
13 open-end wrench.
If a relief duct is fi tted, also unscrew the 12 M8 bolts
(DIN 933) for anchoring the assembly to the relief duct,
located at the bottom rear.
Figure 5.5.
Anchoring bolt position relief duct with
enclosure
Figure 5.6.
Bolt position inside the cable compartment
4.
Remove the external enclosure, lifting it around 100
mm, and withdraw toward the rear section using slings
or chains secured to the side lifting brackets at the top
of the enclosure. The angle of pull must be as vertical
as possible (with an angle greater than 60º from the
horizontal).
Maximum weight of the enclosure: 300 kg.
Figure 5.7.
Removing the external enclosure