Chapter 5 Basic Operation and Test Run
JT550 Series inverter Manual
- 42 -
Figure 5.3 Inverter’s Adjustment Sub-Process Flow (Vector Control)
5.5 Initialization of Parameters
Restore all of settings to default values. After the initialization, F0.24 is automatically set to 0.
F0.24
Restore Default Settings
Range
:
0~501
Default
:
0
1: Restore default settings except motor parameters
If F0.24 is set to 1, most function codes are restored to the default settings except motor
parameters,
frequency reference resolution, errors records, accumulated operating time,
accumulated power-on time
and accumulated power consumption .
2: Clear records
If F0.24 is set to 2, the fault records, accumulated running time , accumulated power-on time and
accumulated power consumption are cleared.
5.6 Operation Commands Source Selection
F0.02
Command Source Options
Range
:
0~2
Default
:
0
0: Operation panel control
Commands are given by pressing keys “RUN,STOP”on the operation panel.
1: Terminal control
Commands are given by means of multifunctional input terminals with functions such as “FWD, REV,
JOGF, and JOGR”.
2: Communication control
Commands are given from the host computer.