Chapter 7 Maintenance and Troubleshooting
- 107 -
F9.47
Fault protection action
selection 1
Range:0000~2222
Default:0000
Ten thousand's
digit(Communicat
ion fault, Err16)
Thousand's digit
(External
equipment fault,
Err15)
Hundred's digit
(Power output
phase loss, Err13)
Ten's digit (Power
input phase loss,
Err12)
Unit's
digit :(Motor
overload,
Err11)
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
0: Coast to stop
1:Stop
according to
the stop mode
2: Continue to
run
F9.48
Fault protection
action selection 2
Range:0000~2222
Default:0000
Ten thousand's
digit(accumulative
running time
reached)
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
Thousand's digit:
reserved
Hundred's digit:
reserved
Ten's digit
(EEPROM
read-write fault,
Err21)
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
Unit's digit
(Encoder fault,
Err20)
0: Coast to stop
1:Stop
according to
the stop mode
2:Continue to
run
F9.49
Fault protection action
selection 3
Range:0000~2222
Default:0000
Ten thousand's
digit (PID
feedback lost
during running)
Thousand's digit
(Load becoming 0,
Err30)
Hundred's digit
(Accumulative
power-on time
reached, Err29)
Ten's digit
(User-defined
fault 2, Err28)
Unit's digit
(User-defined
fault 1,Err27)
0: Coast to stop
1:Stop according
to the stop mode
2:Continue to run
0: Coast to stop
1: Stop according to
the stop mode
2: Continue to run
at 7% of rated
motor frequency
and resume to the
set frequency if the
load recovers
0: Coast to stop
1:Stop according
to the stop mode
2: Continue to run
0:Coast to stop
1:Stop according
to the stop mode
2: Continue to
run
0:Coast to stop
1:Stop
according to
the stop mode
2:Continue to
run
0: Coast to stop
inverter displays Err **, and directly down
1: Stop according to the stop mode
Drive Show A **, then stop mode, the display Err ** after the shutdown.
2: Continue to run
The drive continues to run and display A **, the operating frequency is set by F9.54.
F9.50
Fault protection action
selection 4
Range:000~222
Default:000
Ten's digit (Motor over-speed,Err43)
Unit's digit (Too large speed deviation,Err42)
0: Coast to stop
1:Stop according to the stop mode
2: Continue to run
0: Coast to stop
1:Stop according to the stop mode
2: Continue to run