Chapter 7 Maintenance and Troubleshooting
- 131 -
When Fd.05 is 0 (Non-Standard Modbus Protocol):
ADR
01H
CMD
03H
Byte Count High Bit
00H
Byte Count Low Bit
02H
F003H High Bit
00H
F003H Low Bit
04H
CRC CHK Low Bit
E5
CRC CHK High Bit
C9
When Fd.05 is 1 (Standard Modbus Protocol):
ADR
01H
CMD
03H
Byte Count Low Bit
02H
F003H High Bit
00H
F003H Low Bit
04H
CRC CHK Low Bit
B9
CRC CHK High Bit
87
2) Command Code 06H. Write 1 word.
Function: Write the data of a word to the designated data address in order to modify the parameters
of inverter.
For example: Write 5000(1388H) to the address F00A ([F0.10]) of Inverter (Slave address: 01H).
This frame is described as the following:
Host Command Information:
ADR
01H
CMD
06H
Data Address High Bit
F0H
Data Address Low Bit
0AH
Data Content High Bit
13H
Data Content Low Bit
88H
CRC CHK Low Bit
CRC CHK’s value to be
calculated
CRC CHK High Bit
Slave Response Information:
ADR
01H
CMD
06H
Data Address High Bit
F0H
Data Address Low Bit
0AH
Data Content High Bit
13H
Data Content Low Bit
88H
CRC CHK Low Bit
97
CRC CHK High Bit
9E