Instruction Manual
VLB-92 Omni Mega LED Beacon
© Sabik Oy, Dec 2018
VLB-92 Omni Mega LED Beacon
Page 24 of 56
VLB-92 V1.19
Operation
Feature
Value
1 =
Program
Mode
9 = Read
Settings
5 = Operation Mode
001
– Normal Operation, Failure Mode = Failsafe: Beacon
stops operating when error detected.
002
– Normal Operation, Failure Mode = “Best Effort”
operation: Continue to operate in possibly diminished
capacity
– may result in loss of some intensity from
beacon.)
005
– Beacon On output test, asserts for 10 seconds.
006
– AIS Beacon On output test, asserts for 10 seconds.
007
– Alarm test, asserts Beacon Fail for 10 seconds.
008
– Test Mode for 4 minutes (beacon ignores day off
status and operates continually). Temporary Mode (will
reset to 001 or 002 after execution).
6 = Programming
Mode/IRDA/(RS232
always on)
Default 000
000
– IRDA Disabled, No Monitoring (Default)
001
– IRDA Enabled, No Monitoring
002
– IRDA Monitoring Output, Free Running
003
– IRDA On-demand Monitoring Output
004
– RS232 Free-running Monitoring Output
005
– RS232 Monitoring on Demand Output
006
– RS232, Intermittent (6s) Monitoring in AIS format
7 = Slave Mode Flash
count on loss of
sync
Default 001
1 Character cycle
0YY
– Continue “Y” number of cycles (0-99)
999
– Disabled, never stop flashing
8 = Set Low battery
threshold
24V version:
Default 200, 20.0VDC
12V version:
Default 100, 10.0VDC
YYY
– Battery low threshold.
(24V version: 00.0 to 24.0, or 12V version: 00.0 to 12.0)
999
– Disabled, No battery low cut off
9 = Set High battery
threshold
24V version:
Default 256, 25.6VDC
12V version:
Default 128, 12.8VDC
YYY
– Battery high threshold.
(24V version: 20.1 to 28.0, or 12V version: 10.1 to 14.0)
999
– Default setting (25.6)