L
evel
S
ignal current
-
S
ensor
C
ontrol lamp
F
alling characteris
-
tics max
.
>=
2
.
2
m
A
F
alling characteris
-
tics max
.
<=
1
m
A
R
ising characteris
-
tics min
.
>=
2
.
2
m
A
R
ising characteris
-
tics min
.
<=
1
m
A
F
ailure
any
<=
1
m
A
fl
ashes
6
.
4
R
ecurring function test
A
ccording to
IEC
61508
.
VEGAWAVE
63
is quali
fi
ed in mode
A
(
over
fi
ll protection
)
for
use in measuring chains of stage
SIL
2
according to
IEC
61508
(
redundant
,
stage
SIL
3
).
T
he following instrument combinations meet the requirements
according to
SIL
:
VEGAWAVE
63
l
O
scillator
WE
60
N
T
he recurring test according to
IEC
61508
can be carried out
by pushing the simulation key on the oscillator or by brie
fl
y
(
>
2
seconds
)
interrupting the cable to the sensor
.
T
he correct
sequence of the switching conditions must be monitored via
the switching ampli
fi
er as well as the connected systems
.
T
he
sensor must neither be removed nor response must be
triggered by
fi
lling the vessel
.
T
his applies to
VEGAWAVE
63
with
NAMUR
oscillator
WE
60
N
.
SIL
R
ecurring function test
22
VEGAWAVE
63
- -
NAMUR
S
etup
32259
-
EN
-
070117