5 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
The following reset functions are available:
Reset - Factory settings:
Restores the factory parameters settings as well as the order-specific
settings at the time of delivery. A user-set measuring range is reset to
the recommended measuring range, see chapter "
Technical data
".
A created false signal suppression, freely programmed lineariza-
tion curve as well as measured value and echo curve memories are
cleared. The event and parameter changes memories are retained.
Reset - Restart:
Is used to restart the device without switching off the supply voltage.
Note:
For the duration of the reset, the device changes its behaviour from
the normal measuring operation. Therefore, observe for downstream
systems:
•
The current output outputs the set false signal
•
The Asset-Management function outputs the message "
Mainte-
nance
" aus