5 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment module
Releasing the sensor adjustment is also possible in any menu item by
entering the PIN.
Caution:
When the adjustment is blocked, the adjustment via PACTware/DTM
and other systems is also blocked.
5.2.2 Setup
This menu item allows you to adapt the sensor to the different meas-
uring conditions of the media "
Liquid
" or "
Bulk solid
".
The corresponding application is selected in the following menu item
"
Application
".
Through this selection the operating range of the sensor is adapted
to the vessel height. Hence the measurement reliability is increased
considerably under different basic conditions.
Note:
Regardless of this, the min. adjustment must also be carried out (see
following section).
Since the radar sensor is a distance measuring instrument, it is the
distance from the sensor to the medium surface that is measured. To
indicate the actual level, the measured distance must be assigned to
a certain height percentage (min./max. adjustment).
During adjustment, enter the respective measuring distance when the
vessel is full and empty (see the following examples):
Type of medium
Vessel height
Adjustment