12
5 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
Liquids:
100%
0%
0,5
m
(19.68
")
5
m
(196.
9")
2
1
3
Fig. 10: Parameterisation example min./max. adjustment - liquids
1 Min. level = max. meas. distance (distance B)
2 Max. level = min. meas. distance (distance A)
3 Reference plane
Bulk solids:
2
1
3
100%
0%
1
m
(39.37
")
35
m
(1378
")
Fig. 11: Parameterisation example min./max. adjustment - bulk solids
1 Min. level = max. meas. distance (distance B)
2 Max. level = min. meas. distance (distance A)
3 Reference plane
If these values are not known, and adjustment can for example be
carried out with the distances of 10 % and 90 %.
The starting point for these distance specifications is always the refer-
ence plane, i.e. the sealing surface of the thread or flange. Information